Useful Reference:

more details see: https://docs.oracle.com/cd/E19217-01/819-1177-18/cref_shm.html 

But for different ATCA brand, the clia cmd may be different. Could always "clia help" 

Change RTM Current Threshold:

LinkAgg Board C01-01

  1. clia setthreshold 82 0:17 unr 3.088

  2. clia setthreshold 82 0:17 uc 2.832

  3. clia setthreshold 82 0:17 unc 2.576

LinkAgg Board C01-03

  1. clia setthreshold 86 0:17 unr 3.088

  2. clia setthreshold 86 0:17 uc 2.832

  3. clia setthreshold 86 0:17 unc 2.576


Reset board

clia boardreset <slot>

The above might not work for the link aggregator board. For that, try:

clia deactivate board <slot>

clia activate board <slot>


Change Fan setting:


check fan state:

clia fans   
clia shelf fans_state

disable auto fan:


clia setfanpolicy 20 6 disable
clia setfanpolicy 20 7 disable
 
clia getfanpolicy 20 6 –s
clia getfanpolicy 20 7 –s

set fan min level:

 clia minfanlevel 20 6 2

clia minfanlevel 20 7 2


set fan level:

clia setfanlevel 20 6 2

clia setfanlevel 20 7 2