more details see: https://docs.oracle.com/cd/E19217-01/819-1177-18/cref_shm.html
But for different ATCA brand, the clia cmd may be different. Could always "clia help"
LinkAgg Board C01-01
clia setthreshold 82 0:17 unr 3.088
clia setthreshold 82 0:17 uc 2.832
clia setthreshold 82 0:17 unc 2.576
LinkAgg Board C01-03
clia setthreshold 86 0:17 unr 3.088
clia setthreshold 86 0:17 uc 2.832
clia setthreshold 86 0:17 unc 2.576
clia boardreset <slot>
The above might not work for the link aggregator board. For that, try:
clia deactivate board <slot>
clia activate board <slot>
clia fans
clia shelf fans_state
clia setfanpolicy 20 6 disable
clia setfanpolicy 20 7 disable
clia getfanpolicy 20 6 –s
clia getfanpolicy 20 7 –s
clia minfanlevel 20 6 2
clia minfanlevel 20 7 2
clia setfanlevel 20 6 2
clia setfanlevel 20 7 2