Names are broken down into the standard parts, DeviceType : Area : Position :  Instance (Where needed) : Attribute.

RTD sensors placed on a device, will take the device name specified in the MAD deck.

Device Type

ACCL

Used for everything in the RF system that is part of the general physics and operations interface at the cavity level.

Also used for penetration

GUNUsed for everything in the gun
COLL

Used for Collimators

WIREUsed for Fast wire scanners
TOROUsed for ICT
FARC

Used for Faraday Cup

ROOMUsed for Air sensors in tunnel/building
LLRFUsed for phase reference line
WATRWater system


Area, Subset of Accelerator With RF Devices

See https://slacspace.slac.stanford.edu/sites/lcls/lcls-2/wd/dsg/Forms/AllItems.aspx, Naming Convention section 6.1.2.2

All AREA field are taken from the document.

 

Attribute

Attributes that comprise the physics interface. Scalar unless otherwise specified

  R/WNameDescription
  RTEMPMeasured temperature from PLC(degC)
  RFLOWMeasured flow from PLC(GPM)
  RPRLTEMP

Measured temperature from PLC for Phase reference Line(degC)

  RPENTEMPMeasured temperature from PLC for cable penetration(degC)
  WHLIMDESHigh limit for interlock Sensor
  WLLIMDESLow limit for interlock Sensor
  WBYPBypass request for interlock sensor
  RBYPSTATBypass readback for interlock sensor
  WRESETRest interlock Fault
  RALARMInterlock Alarm Status

 

Attributes highlighted in Bold will be only present for sensors interlocked for MPS. These attributes in bold will be appended to the temperature or flow signal. eg:

SOLN:GUNB:212:FLOWHLIMDES

SOLN:GUNB:212:TEMPHLIMDES

 