Names are broken down into the standard parts, DeviceType : Area : Position :  Instance (Where needed) : Attribute.

RTD sensors placed on a device, will take the device name specified in the MAD deck.

Device Type

ACCL

Used for everything in the RF system that is part of the general physics and operations interface at the cavity level.

Also used for penetration

GUNUsed for everything in the gun
COLL

Used for Collimators

WIREUsed for Fast wire scanners
TOROUsed for ICT
BENDUsed for Magnet
BLMO 
FARC

Used for Faraday Cup

ROOMUsed for Air sensors in tunnel/building
LLRFUsed for phase reference line
WATRWater system


Area, Subset of Accelerator With RF Devices

See https://slacspace.slac.stanford.edu/sites/lcls/lcls-2/wd/dsg/Forms/AllItems.aspx, Naming Convention section 6.1.2.2

All AREA field are taken from the document.

 

Position

See https://slacspace.slac.stanford.edu/sites/lcls/lcls-2/wd/dsg/Forms/AllItems.aspx, Naming Convention section 6.1.2.3.2

Here is a list of all the signals. PV Names can be found in column V

https://slacspace.slac.stanford.edu/sites/lcls/lcls-2/as/controls/CD2/FI_TM/Installation/RTD%20Pigtail%20Organizer%201_22_19.xlsx

 

Attribute

Attributes that comprise the physics interface. Scalar unless otherwise specified

  R/WNameDescription
  RTEMPMeasured temperature from PLC(degC)
  RFLOWMeasured flow from PLC(GPM)
  RPRLTEMP

Measured temperature from PLC for Phase reference Line(degC)

  RPENTEMPMeasured temperature from PLC for cable penetration(degC)
  WHLIMDESHigh limit for interlock Sensor
  WLLIMDESLow limit for interlock Sensor
  WBYPBypass request for interlock sensor
  RBYPSTATBypass readback for interlock sensor
  WRESETRest interlock Fault
  RALARMInterlock Alarm Status

 

Attributes highlighted in Bold will be only present for sensors interlocked for MPS. These attributes in bold will be appended to the temperature or flow signal. eg:

SOLN:GUNB:212:FLOWHLIMDES

SOLN:GUNB:212:TEMPHLIMDES

Some Non Mad sensors:

Room air , water and phase reference line sensor:

RTD Z location is co-related with https://slacspace.slac.stanford.edu/sites/lcls/lcls-2/as/controls/CD2/General/Naming/LCLS-II_Device_Names.xlsx (see AreaStartandEnd Tab for detail) to find the area name. The position field uses numbers ranging from 1 to 99 depending upon the instance of the sensor in the area. See See https://slacspace.slac.stanford.edu/sites/lcls/lcls-2/wd/dsg/Forms/AllItems.aspx, Naming Convention section 6.1.1 for detail.

 

Penetration sensor.

penetration Z location is co-related with https://slacspace.slac.stanford.edu/sites/lcls/lcls-2/as/controls/CD2/General/Naming/LCLS-II_Device_Names.xlsx (see AreaStartandEnd Tab for detail) to find the area name. The position field uses numbers ranging from 1 to 99 depending upon the instance of the penetration in the area. (please note all though penetrations are names with sector names, we will only use that as a description, but use area names as defined in the document above for the PV.)

Instance field will be used for penetration sensors as each penetration will have qty 3-6 sensors installed.