Full recovery, from e.g. a CPU reboot or power outage

  1. Check that CPU should be is up, Master verify master source IOCs sioc-sys0-ms0[1..6] should be are running
    1. See Troubleshooting
  2. Open the MS/PRL main display
    1. See Displays
  3. Ensure Verify that the MO is locked
    1. See MOLocker
  4. Ensure Verify that all power amps are at their target power levels
    1. See PRLAmps
    2. Note: If chassis have been power cycled, there may be a discrepancy between the amp power and the attenuator setpoint.  See Troubleshooting.
  5. Verify Ensure that PRL loops are locked
    1. See PRLLoops

...