Full recovery, from e.g. a CPU reboot or power outage
- Check that CPU is up, verify master source IOCs sioc-sys0-ms0[1..6] are running
- See Troubleshooting
- Open the MS/PRL main display
- See Displays
- Verify that the MO is locked
- See MOLocker
- Verify that all power amps are at their target power levels
- See PRLAmps
- Note: If chassis have been power cycled, there may be a discrepancy between the amp power and the attenuator setpoint. See Troubleshooting.
- Verify that PRL loops are locked
- See PRLLoops