Ensure retry count is reduced to 1

 SLIT Y:



 SLIT Y:

No physical limit switches on these slits.

10/10/2022: Position limits:

  • 15.09mm (High limit)
  • 10.06mm(MPS is NOT IN for IN limit switch)
  • 10.05mm (MPS is IN for IN limit switch)
  • 2.5mm (MPS is NOT OUT for OUT Limit switch)

9/9/2022: Position limits:

  • 15.15.478 mm (High limit)
  • Low limit did not check
  • HomeF: went into zero position positive direction

...

Do Not home the SLITS. Slowly jog to the limit and set the position from motor record.

For regular moves, use 0.2mm/sec speed

Ensure retry count is reduced to 3


BOD1 X:

  • 55.0591 mm (High limit) – all the way in, towards the aisle
  • 32.9278 mm (Low limit)

...