Useful info on SXRSS station (previous version), including motor controller manuals: https://slacspace.slac.stanford.edu/sites/controls/Pages/controls_ops_maint_docs.aspx?RootFolder=%2Fsites%2Fcontrols%2FControls%20Operations%20and%20Maintenance%20Documents%2FSXRSS&FolderCTID=0x012000744B460676FF8B4E93C32481DA33D454&View={B1383413-F36B-4C80-A458-99D04B3253F7}
SLIT X
No physical limit switches on these slits.
02/02/2024: Position limits:
Slit fiducialization motion measurements in Jan/24/2024 can refer to slide: Slit_fiducialization_motion.pptx (sharepoint.com)
- 0.915mm (High limit)
- -1.292mm (Low limit)
10/10/2022: Position limits:
- 2.34mm (High limit)
- -0.3mm (Low limit)
9/9/2022: Position limits:
- 0.938 mm (High limit)
- -1.547 mm (Low limit)
For regular moves, use 0.2mm/sec speed
Ensure retry count is reduced to 1
When the motor is power cycled, the motor needs to be calibrated and homed by following the instructions:
![](/download/thumbnails/358229194/image-2024-2-2_14-34-53.png?version=1&modificationDate=1706913293687&api=v2)
-------------------------------------------------------------------------------------------------------------------------------
SLIT Y:
No physical limit switches on these slits.
02/02/2024: Position limits:
Slit fiducialization motion measurements in Jan/24/2024 can refer to slide: Slit_fiducialization_motion.pptx (sharepoint.com)
- 15.455mm (High limit)
- P6: Stay clear position: 15.4mm
- Sapphire lower edge: 5.350mm
- P5: Sapphire middle: 2.3mm
- Sapphire Upper edge: -0.750mm
- P4: Slit 5: -7.950mm
- P3: Slit 4: -9.450mm
- P2: Slit 3: -10.950mm
- P1: Slit 2: -12.450mm
- P0: Slit 1: -13.950mm
![](/download/attachments/358229194/image-2024-2-2_12-58-25.png?version=1&modificationDate=1706907505066&api=v2)
10/10/2022: Position limits:
- 15.09mm (High limit)
- 10.06mm(MPS is NOT IN for IN limit switch)
- 10.05mm (MPS is IN for IN limit switch)
- 2.5mm (MPS is NOT OUT for OUT Limit switch)
9/9/2022: Position limits:
- 15.478 mm (High limit)
- Low limit did not check
- HomeF: went into zero position positive direction
For regular moves, use 0.2mm/sec speed
Ensure retry count is reduced to 3
When the motor is power cycled, the motor needs to be calibrated and homed by following the instructions:
![](/download/thumbnails/358229194/image-2024-2-2_14-35-17.png?version=1&modificationDate=1706913317579&api=v2)
In addition, a slit target positions GUI is added for users convenience, they can just press P* buttons to move the motor to setting positions.
![](/download/attachments/358229194/image-2024-2-2_14-40-2.png?version=1&modificationDate=1706913602462&api=v2)
-------------------------------------------------------------------------------------------------------------
BOD1 X:
9/27/2022: Position limits: after rotation!
- 55.0332 mm (High limit) – aisle side limit;
- 32.9301 mm (Low limit) - wall side limit;
NEED to confirm what value is OUT of beam
9/9/2022: Position limits:
- 55.0591 mm (High limit) – wall side limit; out of beam
- 32.9278 mm (Low limit) - aisle side limit
---------------------------------------------------------------------------------------------------------------
BOD1 Y:
9/27/2022: Position limits: after rotation!
9/9/2022: Position limits:
- 23.3240 mm (High limit) - top limit
- 20.9312 mm (Low limit) -bottom limit
------------------------------------------------------------------------------------------------------------------
M3Pitch and M3Yaw
Motors were not driven to the limit switch. Only to the position where alignment was able to give data. So when the device is IN(?)
M3P: Moved from 36.6 to 38mm
M3Y: Moved from 34.7 to 35.9mm
Disable Torque on M3Y while moving the motor M3P.
Disable Torque on M3P while moving M3Y.