- 0.938 mm (High limit)
- -1.547 mm (Low limit)
Can use HomeR or HomeF – Forward homes it to 0.3mm and Reverse homes it to 0.0mm
Do not HOME the motor. It homes very fast
For regular moves, use 0.2mm/sec speed
Ensure retry count is reduced to 1
When the motor is power cycled, the motor needs to be calibrated and homed by following the instructions:
Image Added
-------------------------------------------------------------------------------------------------------------------------------
...
- P2: Slit 3: -10.950mm
- P1: Slit 2: -12.450mm
- P0: Slit 1: -13.950mm
Image Added
10/10/2022: Position limits:
...
- 15.478 mm (High limit)
- Low limit did not check
- HomeF: went into zero position positive direction
Do Not home the SLITS. Slowly jog to the limit and set the position from motor record.
For regular moves, use 0.2mm/sec speed
Ensure retry count is reduced to 3
When the motor is power cycled, the motor needs to be calibrated and homed by following the instructions:
Image Added
In addition, a slit target positions GUI is added for users convenience, they can just press P* buttons to move the motor to setting positions.
Image Added
-------------------------------------------------------------------------------------------------------------
...