The following sections describe the PV names for PEPPEx motion control stage. The device is composed of two movable axis. One in Y direction with a total movable range of 82 mm and one in X axis with total movable range of 8 mm.


Y Axis:

The Zone plates are on the Y axis. Only one at a time can be inserted. There are 4 zone plates, ordered from the first inserted to the last as the actuator moves from its nominal "Zero" position. Zero position is at the out/upper limit switch and the axis moves in negative direction as is grows into the beam.


PVs related to mover as a whole

MOVR:UNDS:5013:Y:ENABLE

Enable motor torque

MOVR:UNDS:5013:Y:ENABLEDSTAT

motor torque status

MOVR:UNDS:5013:Y:MOTR.VAL

motor record - requested position

MOVR:UNDS:5013:Y:MOTR.RBV

motor record - readback position

MOVR:UNDS:5013:Y:MovingBinary PV indicating if mover is moving or not

MOVR:UNDS:5013:Y:EncRdbk

BissC Encoder Readback
MOVR:UNDS:5013:Y:EncOffsetAbsolute Encoder Offset
MOVR:UNDS:5013:Y:DISABLE

Disable motor torque


X Axis:


The actuator moves in negative X direction towards the aisle. The nominal Zero position will be the center of the first inserted zone plate into the beampath.


PVs related to mover as a whole

MOVR:UNDS:5013:X:ENABLE

Enable motor torque

MOVR:UNDS:5013:X:ENABLEDSTAT

motor torque status

MOVR:UNDS:5013:X:MOTR.VAL

motor record - requested position

MOVR:UNDS:5013:X:MOTR.RBV

motor record - readback position

MOVR:UNDS:5013:X:HomeOffsetDistance from beam centerline to aisle limit switch
MOVR:UNDS:5013:X:MovingBinary PV indicating if mover is moving or not
MOVR:UNDS:5013:X:EncRbdkBissC Encoder Readback
MOVR:UNDS:5013:X:EncOffsetAbsolute Encoder Offset
MOVR:UNDS:5013:X:DISABLE

Disable motor torque


Test Information from B31

X axis maximum speed attained 1mm/sec

Y axis maximum speed attained 0.75mm/sec


When X axis moves in CW direction (looking at the rear shaft of the motor or looking from aisle side) the paddle moves into the beam.


Data from alignment (Pre installation from B31)


Zone PlateX (mm)Y (mm)
Zone Plate 0 center0-31.7783
Zone Plate 1 center-0.0194-46.2797
Zone Plate 2 center0.1694-60.3538
Zone Plate 3 center0.4287-74.7899


Motion End of Travel limit positions from alignment (Pre installation from B31)

Limit Switchposition (mm)
Y Axis Motion End of travel limit (Top)0
Y Axis Motion End of travel limit (Bottom)-81.5293
X Axis Motion End of travel limit (CCW label)4.0418
X Axis Motion End of travel limit (CW label)-4


MPS limit positions from alignment (Pre installation from B31)

Limit SwitchStart Trip point (mm)End Trip point (mm)
MPS Out0-3.8244
MPS 0-28.262-35.799
MPS 1-42.611-50.221
MPS 2-56.988-64.621
MPS 3-71.380-78.655


IOC Configuration

sioc-unds-mc03IOC Name
moc-unds-mc48MOC Name
motion/motionAppsource code location

acsw-unds-nw50

port 1


Aerotech requirements

resoluteEncoder.abi reads back data from DRIVEINFO field ResoluteAbsolutePosition. This program needs to be autorun in Task1 so that data can be read in EPICS

parameterNames.cfg must be loaded in the file system


Aerotech parameters setup

X axis

Counts/unit

Encoder = 50nm resolution => 1 count of encoder = 5 * 10^(-5) mm

In Aerotech for mm as unit

Counts/unit = 1/ (5* 10^(-5)) = 20000


Counts/rev

1 motor revolution = 1.27 mm

=> 20000*1.27 = 25400


Parameters that affected in lowering the chriping noise

Running current = 0.5A

Holding current = 0.2A

Stepper Damping Cut off = 150


Y axis


Counts/unit

Encoder = 50nm resolution => 1 count of encoder = 5 * 10^(-5) mm

In Aerotech for mm as unit

Counts/unit = 1/ (5* 10^(-5)) = 20000


Counts/rev

Y axis seems to have a gear reducer 5:1 added

5 motor revolution = 1.27 mm

=> 20000*1.27/5 = 5080


Parameters that affected in lowering the chriping noise

Running current = 2A

Holding current = 0.5A

Stepper Damping Cut off = 80


Max Speed

X axis maximum speed attained 1mm/sec

Y axis maximum speed attained 0.75mm/sec


Error Thresholds

InPositionDistance (the position error threshold below which an axis is considered to be in position) for both axis 10-5 mm

InPositionTime (quantity of time that the position error of the axis must be less than InPositionDistance)  = 500 sec

PositionErrorThreshold ( maximum allowable position error (the difference between the position command and the position feedback) before a position error fault is generated.)

1mm


  • No labels