Naming Conventions for Vacuum Devices
Base Device Type
First, lets consider the base DeviceType values without the detail suffix.
The following table lists vacuum Compound DeviceTypes:
Value |
Device Type |
SLC Aware |
Controllable |
VGBA |
Vacuum Gauge Baratron |
N |
N |
VGKL |
Vacuum Gauge associated with a Klystron |
N |
N |
VGPR |
Vacuum Pirani Gauge |
N |
N |
VGCC |
Vacuum Cold Cathode Gauge |
N |
Y |
VGTC |
Vacuum ThermoCouple Gauge |
N |
N |
VGCP |
Vacuum Convection-enhanced Pirani Gauge |
N |
N |
VGHF |
Vacuum Hot Filament Gauge |
N |
Y |
VGOS |
Vacuum Overpressure Switch |
N |
N |
VVKL |
Vacuum Valve associated with a Klystron |
N |
Y |
VVPG |
Vacuum Pneumatic Gate Valve |
N |
Y |
VVMG |
Vacuum Manual Gate Valve |
N |
N |
VVPR |
Vacuum Pneumatic Roughing Valve |
N |
Y |
VVMR |
Vacuum Manual Roughing Valve |
N |
N |
VVPF |
Vacuum Pneumatic Fore Valve |
N |
Y |
VVMF |
Vacuum Manual Fore Valve |
N |
N |
VVPV |
Vacuum Pneumatic Vent Valve |
N |
Y |
VVMV |
Vacuum Manual Vent Valve |
N |
N |
VVFS |
Vacuum Fast (Shutter) Valve |
N |
Y |
VVFL |
Vacuum (Mass) Flow Valve |
N |
Y |
VPKL |
Vacuum Pump associated with a Klystron |
N |
Y |
VPCR |
CRyo Pump |
N |
Y |
VPIO |
IOn Pump |
N |
Y |
VPTM |
TurboMolecular Pump |
N |
Y |
VPTS |
Ti Sublimation Pump |
N |
Y |
VPFO |
Fore Pump |
N |
Y |
VPRO |
Roughing Pump |
N |
Y |
The following table lists vacuum gauge
Attributes:|| Value || Description ||
Unknown macro: {SORT(sort=>asc)}
| |
P |
Pressure |
PSTAT |
Status of pressure relay |
PSTATSPRBCK |
Readback of trip point of pressure relay |
PSTATSPDES |
Set the trip point of the pressure relay |
PSTATEN |
Enable the pressure relay |
PSTATENRBCK |
Status of pressure relay enable |
Unknown macro: {SORT} |
|