Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

  1. Ensure the DPS Watcher is running
  2. Use this procedure to stop the DPS pumps: Turning off Differential Pumping System (DPS)
  3. After the LCW is restored:
    1. Check that water is flowing to the DPS system: From the "DPS Full Schematic", click on a roughing pump icon, then "More...". Confirm the water flow reading is >0 L/min. Nominal is 1.3 to 2.1 L/min.
    2. Use this procedure to restart the DPS pumps: Restarting DPS pumps#StartingorRestartingtheDPSpumpswhenthebeamlineisundervacuum
  4. Confirm the S20 vacuum is returned to the nominal state, as shown below.

...

  1. :

DPS under nominal conditions

...

Image Added


Layout of the LCW system feeding the DPS pumps

The DPS pumps require the LCW water pressure to be reduced from nominal LCW pressure of ~180psi to around ~60psi. This is done by a pressure regulator in the gallery at penetration 20-10 - pointed at in the image below. The water is transported down the penetration through the insulated pipe.  Note that the inline valve to the lower left of the regulator should be open.

Image Added


In the tunnel, the water is split off towards the upstream and downstream DPS systems.

Image coming soon...


Water flows in parallell to each of the turbos/roughing pumps on each side of the DPS, flowing from a supply manifold, through the pumps, then back to the return manifold. Upstream and downstream manifolds are shown below.

Image coming soon...


The return feeds back into the main return water manifold on the tunnel ceiling.

Image coming soon...