Power Estimation

Estimate: test run measured values
Nominal: APV25 current draw
Maximum: maximum from APV25 manual

System

Estimate (W)

Nominal (W)

Maximum (W)

FE Boards

85

100

140

Hybrids

75.6

140.4

298.8

Radiative load (from #1)9.4 50

 

Simple estimate of radiative load on support plates

#1: Radiative load - Pelle

Requirements

  • Temperature
    • Sensor temperature -10C (support plate temperature approx. -20C)
    • DAQ boards should be at room temperature at nominal power i.e.  approx. +20C
  • Mechanical
    • Three cooling loops for DAQ (FE board support), L1-3 and L4-6 module support plates (no manifold inside vacuum box, for 2014 one 8" side flange of the vacuum box is available for cooling lines)
  • Heat load
    • 190W combined maximum heat load on L1-3 and L4-6 cooling
    • 100W maximum heat load on DAQ cooling

Hybrid power consumption

FE board power consumption

  • No labels