1. EPICS IOC Prepared
    1. SXR IOC Configuration:
      1. git repo: Undulator_SXR
        1. branch: epics7-update
      2.  $(git_repo)/configure/RELEASE:
        • SEQ_MODULE_VERSION                =R2.2.4-1.2
          AUTOSAVE_MODULE_VERSION     =R5.8-2.1.0
          CAPUTLOG_MODULE_VERSION     =R4.0-1.0.0
          IOCADMIN_MODULE_VERSION     =R3.1.16-1.3.2
          SSUBRECORD_MODULE_VERSION   =R3.0.4
          MODBUS_MODULE_VERSION       =R3.2-1.0.1
          ASYN_MODULE_VERSION             =R4.39-1.0.1
          MOTOR_MODULE_VERSION         =R6.10.1-2.3.1
          STREAM_MODULE_VERSION        =R2.8.9-1.2.1
          CALC_MODULE_VERSION             =R3.7-1.0.1
          MISCUTILS_MODULE_VERSION    =R2.2.5
          SSCAN_MODULE_VERSION          =R2.10.2-1.0.0
          CEXP_MODULE_VERSION             =R1.1.3
          SPLINE_MODULE_VERSION          =R2.0.2
      3.   $(git_repo)/configure/RELEASE_SITE:
        • BASE_MODULE_VERSION=R7.0.3.1-1.0
          EPICS_SITE_TOP=/afs/slac/g/lcls/epics
          BASE_SITE_TOP=/afs/slac/g/lcls/epics/base
          EPICS_MODULES=/afs/slac/g/lcls/epics/R7.0.3.1-1.0/modules
          IOC_SITE_TOP=/afs/slac/g/lcls/epics/iocTop
          PACKAGE_SITE_TOP=/afs/slac/g/lcls/package
          TOOLS_SITE_TOP=/afs/slac/g/lcls/tools
          ALARM_CONFIGS_TOP=/afs/slac/g/lcls/tools/AlarmConfigsTop
      4.  $(git_repo)/configure/CONFIG_SITE:
        • CHECK_RELEASE = YES

          CROSS_COMPILER_TARGET_ARCHS = 

          PKG_ARCH=$(T_A)

          INSTALL_LOCATION_STARTUP += $(INSTALL_LOCATION)/startup
          DIRECTORY_TARGETS += $(INSTALL_LOCATION_STARTUP)
          SHARED_LIBRARIES=NO
          STATIC_BUILD=YES

          # Location of Kernel Modules
          LINUX_KERNEL_MODULES=$(PACKAGE_SITE_TOP)/linuxKernel_Modules

          LINUX_VERSION=rhel6

           PCRE=YES
           PCRE_PACKAGE_NAME=pcre
           PCRE_VERSION=8.37
           PCRE_TOP=$(PACKAGE_SITE_TOP)/$(PCRE_PACKAGE_NAME)/$(PCRE_VERSION)
           PCRE_LIB=$(PCRE_TOP)/$(PKG_ARCH)/lib
           PCRE_INCLUDE=$(PCRE_TOP)/$(PKG_ARCH)/include

  2. SXR Upgrade Test Plan
    1. Week 1: Practice test on SXU-021
      1. Prepare work:
        1. Record current iocSpecificRelease for sioc-b81-mc03:
          1. iocSpecificRelease -> /u/cd/tthayer/workspace/LCLSII/SXRU/Undulator_SXR_MMF/
      2. During the test day:
        1. Boot current EPICS 3 based IOC, record settings:
        2. Currently sioc-b81-mc03 is running, need to check again before test
        3. Open EDM based Undulator GUI
          1. login lcls-dev3
          2. cd ../tthayer
          3. cd LCLSII/SXRU/Undulator_SXR_MMF/util/prod
          4. ./SXU_TCRM_GUI.sh
        4. Before any movement, record all the settings.
          1. Take screenshots from GUI
          2. check IOC status
          3. check network connection: moc-b81-mc03
          4. Follow  checkout sheet to process the practice tests
        5. Print the checkout sheet
        6. Practice with K value and Gap convert
        7. According to the checkout sheet, the main motion test should be as follows:
          1. Move gap from 180mm to 100mm
          2. Power off controller and turn off ioc
          3. Power on controller and turn on ioc
          4. Confirm Encoder RBD value
          5. Tests will verify the correct operation of the following motion controls:
          6. Wiring, switch status, ESTOP functionality.
          7. Coordinated motion for gap adjustment.
          8. Encoder read back: available, calibrated.
          9. Limit, tilt, and vacuum switches: single axis, coordinated motion.
        8. Take a look on spline
        9. Stop the test if encounter any issue/hazard, contact Alex for help.
      3. After all the test, revert all the settings as same as saved before.
    1. Week 2: EPICS 7 Upgrade test
      1. Prepare work:
        1. Confirm current iocSpecificRelease for sioc-b81-mc03:
          1. iocSpecificRelease -> /u/cd/tthayer/workspace/LCLSII/SXRU/Undulator_SXR_MMF/
        2. Confirm the repo branch "epics7-update" is compatible with current running branch "develop"
      2. During the test day:
        1. Before any movement, record all the settings.
          1. Take screenshots from GUI
          2. check IOC status
          3. check network connection: moc-b81-mc03
        2. change the sioc-b81-mc03's slink to the test repo:
          1. iocSpecificRelease -> /u/cd/zyhuang/source/repos/motionControlApps/Undulator_SXR/Undulator_SXR-git
        3. Reboot IOC
          1. check IOC status
          2. check network connection
          3. check GUI status
          4. check $IOC_DATA/sioc-b81-mc03 and confirm all the iocInfo files (like autosave and screenlog) are generated correclty.
        4. Convert K value and Gap, make sure this function is normal.
          1. Need to convert from K value to Gap and from Gap to K value.
          2. Record the value and compare with last time's test.
        5. Follow  checkout sheet to process the practice tests:
          1. Stop when any issue occurred.Stop, contact Alex for help.
        6. After all the checkout steps are done ,call Alex to come and double check everything is working.
        7. After all the test, revert all the settings as same as saved before.
        8. Stop current IOC and change slink back to:
          1. iocSpecificRelease -> /u/cd/tthayer/workspace/LCLSII/SXRU/Undulator_SXR_MMF/
        9. Confirm all the settings are as same as saved before.
  • No labels