Based on spec cd-ss-pps-07-11-33_RSY_Specification.pdf
Area: RSY
Sub-areas: RS1 to 5, RT1 (trench)
PV | Description | Area | Device | PLC tag/EPICS name | Type | HIGH | LOW | AC to EPICS | EPICS to AC | Similar previous PV name |
PPS:RS1:1:Gate | RS1A gate closed switch | RS1 | proximityswitch | RS1A_GT_CLS_RT | Input | CLOSED | NOT_CLOSED | 0.0 |
|
|
KEY:RS1:1:Preset | Preset 1 key | RS1 | Keyswitch | RS1_PR1_KSW_RT | Input | SET | NOT_SET | 0.1 |
|
|
KEY:RS1:2:Preset | Preset 2 key | RS1 | Keyswitch | RS1_PR2_KSW_RT | Input | SET | NOT_SET | 0.2 |
|
|
KEY:RS1:1:SearchSet | Search Set key | RS1 | Keyswitch | RS1_SRCH_SET_KSW_RT | Input | SET | NOT_SET | 0.3 |
|
|
PPS:RSY:1:Keybank | Keybank complete | RSY | limitswitch | KYBNK_S_CMPLT_RT | Input | COMPLETE | NOT_COMPLETE | 0.4 |
|
|
PPS:RSY:1:KeybankRelease | Key release | RSY | Solenoid | KYBNK_S_REL | Output | ACTIVE | NOT_ACTIVE |
| 24.5 |
|
PPS:RT1:1:Gate | RT1A gate closed switch | RT1 | Limit Switch | RT1A_GT_CLS_RT | Input | CLOSED | NOT_CLOSED | 0.5 |
|
|
PPS:RT1:2:Gate | RT1B gate closed switch | RT1 | Keyswitch | RT1B_GT_CLS_RT | Input | CLOSED | NOT_CLOSED | 0.6 |
|
|
KEY:RT1:1:Preset | Preset 1 key | RT1 | Keyswitch | RT1_PR1_KSW_RT | Input | SET | NOT_SET | 0.7 |
|
|
KEY:RT1:2:Preset | Preset 2 key | RT1 | Keyswitch | RT1_PR2_KSW_RT | Input | SET | NOT_SET | 1.0 |
|
|
KEY:RT1:1:SearchSet | Search Set key | RT1 | Keyswitch | RT1_SRCH_SET_KSW_RT | Input | SET | NOT_SET | 1.1 |
|
|
PLC:B209:1:DC:DC:StatusOkXXXX? | 24V DC Power Supply | RSY | DryContact | EPICS_B209_UPS_DC_OK_RT | input | OK | FAULT | 1.2 |
|
|
PLC:B209:1:DC:UpsFaultStatus | UPS Fault Status | RSY | DryContact | EPICS_B209_UPS_ALARM_RT | input | OK | FAULT | 1.3 |
|
|
PLC:B209:1:DC:UpsMode | UPS Battery Mode | RSY | DryContact | EPICS_B209_UPS_BATT_MODE_RT | input | Battery | Normal | 1.4 |
|
|
PLC:B209:1:DC:UpsCharging | UPS Battery Charging | RSY | DryContact | EPICS_B209_UPS_BATT_CHARGE_RT | input | Charging | Charged | 1.5 |
|
|
PPS:RS2:1:Gate | RS2A gate closed switch | RS2 | proximity sensor | RS2A_GT_CLS_RT | Input | CLOSED | NOT_CLOSED | 1.6 |
|
|
KEY:RS2:1:Preset | Preset 1 key | RS2 | Keyswitch | RS2_PR1_KSW_RT | Input | SET | NOT_SET | 1.7 |
|
|
KEY:RS2:2:Preset | Preset 2 key | RS2 | Keyswitch | RS2_PR2_KSW_RT | Input | SET | NOT_SET | 2.0 |
|
|
KEY:RS2:1:SearchSet | Search Set key | RS2 | Keyswitch | RS2_SRCH_SET_KSW_RT | Input | SET | NOT_SET | 2.1 |
|
|
|
| RS2 | limit switch | RS2_406_SDR_CLS_RT | Input | CLOSED | NOT_CLOSED | 2.2 |
|
|
|
| RS2 | limit switch | RS2_406_WDR_CLS_RT | Input | CLOSED | NOT_CLOSED | 2.3 |
|
|
KEY:B406:1:Preset | B406 Preset 1 key | RS2 | Keyswitch | RS2_406_PR1_KSW_RT | Input | SET | NOT_SET | 2.4 |
|
|
KEY:B406:2:Preset | B406 Preset 2 key | RS2 | Keyswitch | RS2_406_PR2_KSW_RT | Input | SET | NOT_SET | 2.5 |
|
|
|
| RS2 | limit switch | RS2_407_SDR_CLS_RT | Input | CLOSED | NOT_CLOSED | 2.6 |
|
|
|
| RS2 | limit switch | RS2_407_NDR_CLS_RT | Input | CLOSED | NOT_CLOSED | 2.7 |
|
|
|
| RS2 | limit switch | RS2_407_EDR_CLS_RT | Input | CLOSED | NOT_CLOSED | 3.0 |
|
|
KEY:B407:1:Preset | B407 Preset 1 key | RS2 | Keyswitch | RS2_407_PR1_KSW_RT | Input | SET | NOT_SET | 3.1 |
|
|
KEY:B407:1:Preset | B407 Preset 2 key | RS2 | Keyswitch | RS2_407_PR2_KSW_RT | Input | SET | NOT_SET | 3.2 |
|
|
PPS:RS2:1:Gate | RS3A gate closed switch | RS3 | proximity sensor | RS3A_GT_CLS_RT | Input | CLOSED | NOT_CLOSED | 3.3 |
|
|
PPS:RS2:2:Gate | RS3B gate closed switch | RS3 | proximity sensor | RS3B_GT_CLS_RT | Input | CLOSED | NOT_CLOSED | 3.4 |
|
|
PPS:RS2:3:Gate | RS3C gate closed switch | RS3 | ez connector | RS3C_GT_CLS_RT | Input | CLOSED | NOT_CLOSED | 3.5 |
|
|
KEY:RS3:1:Preset | Preset 1 key | RS3 | Keyswitch | RS3_PR1_KSW_RT | Input | SET | NOT_SET | 3.6 |
|
|
KEY:RS3:2:Preset | Preset 2 key | RS3 | Keyswitch | RS3_PR2_KSW_RT | Input | SET | NOT_SET | 3.7 |
|
|
KEY:RS3:1:SearchSet | Search Set key | RS3 | Keyswitch | RS3_SRCH_SET_KSW_RT | Input | SET | NOT_SET | 4.0 |
|
|
|
| RS3 | Limit Switch | RS3_911_EDR_CLS_RT | Input | CLOSED | NOT_CLOSED | 4.1 |
|
|
KEY:B911:1:Preset | B911 Preset 1 key | RS3 | Keyswitch | RS3_911_PR1_KSW_RT | Input | SET | NOT_SET | 4.2 |
|
|
KEY:B911:2:Preset | B911 Preset 2 key | RS3 | Keyswitch | RS3_911_PR2_KSW_RT | Input | SET | NOT_SET | 4.3 |
|
|
|
| RS2 | limit switch | RS2_406_RUDR_CLS_RT | Input | CLOSED | NOT_CLOSED | 4.4 |
|
|
|
| RSY | MomentaryButton | ACR_HW_EN_RT | Input | ACTIVE | NOT_ACTIVE | 4.5 |
|
|
|
| RSY | DryContact | RSY_SECURE | Output | OK | FAULT | XXX |
|
|
|
| RSY | Interface | RSY_SECURITY_VIOLATION | Output | OK | FAULT | 4.6 |
|
|
|
| RS4 | Keyswitch | RS4_912_WDR_CLS_RT | Input | CLOSED | NOT_CLOSED | 4.7 |
|
|
KEY:B912:1:Preset | B912 Preset 1 key | RS4 | Keyswitch | RS4_912_PR1_KSW_RT | Input | SET | NOT_SET | 5.0 |
|
|
KEY:B912:2:Preset | B912 Preset 2 key | RS4 | Keyswitch | RS4_912_PR2_KSW_RT | Input | SET | NOT_SET | 5.1 |
|
|
PPS:RS4:1:Gate | RS4A gate closed switch | RS4 | proximity sensor | RS4A_GT_CLS_RT | Input | CLOSED | NOT_CLOSED | 5.2 |
|
|
PPS:RS4:3:Gate | RS4C gate closed switch | RS4 | ez connector | RS4C_GT_CLS_RT | Input | CLOSED | NOT_CLOSED | 5.3 |
|
|
KEY:RS4:2:Preset | Preset 2 key | RS4 | Limit Switch | RS4_PR2_KSW_RT | Input | SET | NOT_SET | 5.4 |
|
|
KEY:RS3:1:SearchSet | Search Set key | RS4 | Keyswitch | RS4_SRCH_SET_KSW_RT | Input | SET | NOT_SET | 5.5 |
|
|
PPS:RS4:2:Gate | RS4B gate closed switch | RS4 | proximity sensor | RS4B_GT_CLS_RT | Input | CLOSED | NOT_CLOSED | 5.6 |
|
|
KEY:RS4:1:Preset | Preset 1 key | RS4 | Keyswitch | RS4_PR1_KSW_RT | Input | SET | NOT_SET | 5.7 |
|
|
|
| RS5 | Limit Switch | RS5_913_SDR_CLS_RT | Input | CLOSED | NOT_CLOSED | 6.0 |
|
|
|
| RS5 | Keyswitch | RS5_913_WDR_CLS_RT | Input | CLOSED | NOT_CLOSED | 6.1 |
|
|
KEY:B913:1:Preset | B913 Preset 1 key | RS5 | Keyswitch | RS5_913_PR1_KSW_RT | Input | SET | NOT_SET | 6.2 |
|
|
KEY:B913:2:Preset | B913 Preset 2 key | RS5 | Keyswitch | RS5_913_PR2_KSW_RT | Input | SET | NOT_SET | 6.3 |
|
|
PPS:RS5:1:Gate | RS5A gate closed switch | RS5 | proximity sensor | RS5A_GT_CLS_RT | Input | CLOSED | NOT_CLOSED | 6.4 |
|
|
PPS:RS5:3:Gate | RS5C gate closed switch | RS5 | ez connector | RS5C_GT_CLS_RT | Input | CLOSED | NOT_CLOSED | 6.5 |
|
|
KEY:RS5:2:Preset | Preset 2 key | RS5 | Limit Switch | RS5_PR2_KSW_RT | Input | SET | NOT_SET | 6.6 |
|
|
KEY:RS5:1:SearchSet | Search Set key | RS5 | Keyswitch | RS5_SRCH_SET_KSW_RT | Input | SET | NOT_SET | 6.7 |
|
|
|
| RSY | DryContact | KYBNK_N_CMPLT_RT | Input | COMPLETE | NOT_COMPLETE | 7.0 |
|
|
PPS:RS5:2:Gate | RS5B gate closed switch | RS5 | proximity sensor | RS5B_GT_CLS_RT | Input | CLOSED | NOT_CLOSED | 7.1 |
|
|
KEY:RS5:1:Preset | Preset 1 key | RS5 | Keyswitch | RS5_PR1_KSW_RT | Input | SET | NOT_SET | 7.2 |
|
|
PPS:RS5:4:Gate | RS5D gate closed switch | RS5 | ez connector | RS5DE_GT_CLS_RT | Input | CLOSED | NOT_CLOSED | 7.3 |
|
|
|
| RSY | Solenoid | KYBNK_N_REL | Output | ACTIVE | NOT_ACTIVE |
| 24.4 |
|
PLC:B209:1:DC:Ok |
| RSY | DryContact | EPICS_B913_UPS_DC_OK_RT | input | OK | FAULT | 7.5 |
|
|
PLC:B209:1:DC:UpsFaultStatus |
| RSY | DryContact | EPICs_B913_UPS_ALARM_RT | input | OK | FAULT | 7.6 |
|
|
|
| RSY | DryContact | EPICS_B913_UPS_BATT_MODE_RT | input | OK | FAULT | 7.7 |
|
|
|
| RSY | DryContact | EPICS_B913_UPS_BATT_CHARGE_RT | input | OK | FAULT | 8.0 |
|
|
|
| RS1 | - | RS1_PR1_LAT | Internal | LATCHED | NOT_LATCHED | 8.1 |
|
|
|
| RS1 | - | RS1_PR2_LAT | Internal | LATCHED | NOT_LATCHED | 8.2 |
|
|
|
| RS1 | - | RS1_SRCH_TMR_ACTV | Internal | ACTIVE | NOT_ACTIVE | 8.3 |
|
|
|
| RS1 | - | RS1A_GT_CLS_ILCK | Internal | CLOSED | NOT_CLOSED | 8.4 |
|
|
|
| RS1 | - | RS1_DIB ACTV | Internal | ACTIVE | NOT_ACTIVE | 8.5 |
|
|
|
| RS1 | - | RS1_SRCH_SET_LAT | Internal | LATCHED | NOT_LATCHED | 8.6 |
|
|
|
| RS1 | - | RS1A_GT_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 8.7 |
|
|
|
| RT1 | - | RT1_PR1_LAT | Internal | LATCHED | NOT_LATCHED | 9.0 |
|
|
|
| RT1 | - | RT1_PR2_LAT | Internal | LATCHED | NOT_LATCHED | 9.1 |
|
|
|
| RT1 | - | RT1_SRCH_TMR_ACTV | Internal | ACTIVE | NOT_ACTIVE | 9.2 |
|
|
|
| RT1 | - | RT1A_GT_CLS_ILCK | Internal | CLOSED | NOT_CLOSED | 9.3 |
|
|
|
| RT1 | - | RT1_DIB_ACTV | Internal | ACTIVE | NOT_ACTIVE | 9.4 |
|
|
|
| RT1 | - | RT1_SRCH_SET_LAT | Internal | LATCHED | NOT_LATCHED | 9.5 |
|
|
|
| RT1 | - | RT1_All_GTS_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 9.6 |
|
|
|
| RT1 | - | RT1A_GT_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 9.7 |
|
|
|
| RT1 | - | RT1B_GT_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 10 |
|
|
|
| RS2 | - | RS2_PR1_LAT | Internal | LATCHED | NOT_LATCHED | 10.1 |
|
|
|
| RS2 | - | RS2_PR2_LAT | Internal | LATCHED | NOT_LATCHED | 10.2 |
|
|
|
| RS2 | - | RS2_SRCH_TMR_ACTV | Internal | ACTIVE | NOT_ACTIVE | 10.3 |
|
|
|
| RS2 | - | RS2A_GT_CLS_ILCK | Internal | CLOSED | NOT_CLOSED | 10.4 |
|
|
|
| RS2 | - | RS2_DIB_ACTV | Internal | ACTIVE | NOT_ACTIVE | 10.5 |
|
|
|
| RS2 | - | RS2_ALL_GTS_DRS_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 10.6 |
|
|
|
| RS2 | - | RS2_SRCH_SET_LAT | Internal | LATCHED | NOT_LATCHED | 10.7 |
|
|
|
| RS2 | - | RS2_406_PR1_LAT | Internal | LATCHED | NOT_LATCHED | 11 |
|
|
|
| RS2 | - | RS2_406_PR2_LAT | Internal | LATCHED | NOT_LATCHED | 11.1 |
|
|
|
| RS2 | - | RS2_406_DIB_ACTV | Internal | ACTIVE | NOT_ACTIVE | 11.2 |
|
|
|
| RS2 | - | RS2_406_PRSVD_SRCH | Internal | SET | NOT_SET | 11.3 |
|
|
|
| RS2 | - | RS2_406_SDR_CLS_ILCK | Internal | CLOSED | NOT_CLOSED | 11.4 |
|
|
|
| RS2 | - | RS2_406_ALL_DRS_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 11.5 |
|
|
|
| RS2 | - | RS2_407_PR1_LAT | Internal | LATCHED | NOT_LATCHED | 11.6 |
|
|
|
| RS2 | - | RS2_407_PR2_LAT | Internal | LATCHED | NOT_LATCHED | 11.7 |
|
|
|
| RS2 | - | RS2_407_DIB_ACTV | Internal | ACTIVE | NOT_ACTIVE | 12 |
|
|
|
| RS2 | - | RS2_407_PRSVD_SRCH | Internal | SET | NOT_SET | 12.1 |
|
|
|
| RS2 | - | RS2_407_SDR_CLS_ILCK | Internal | CLOSED | NOT_CLOSED | 12.2 |
|
|
|
| RS2 | - | RS2_407_ALL_DRS_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 12.3 |
|
|
|
| RS2 | - | RS2A_GT_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 12.4 |
|
|
|
| RS2 | - | RS2_407_NDR_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 12.5 |
|
|
|
| RS2 | - | RS2_407_EDR_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 12.6 |
|
|
|
| RS2 | - | RS2_407_SDR_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 12.7 |
|
|
|
| RS2 | - | RS2_406_WDR_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 13 |
|
|
|
| RS2 | - | RS2_406_SDR_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 13.1 |
|
|
|
| RS2 | - | RS2_406_RUDR_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 13.2 |
|
|
|
| RS3 | - | RS3_PR1_LAT | Internal | LATCHED | NOT_LATCHED | 13.3 |
|
|
|
| RS3 | - | RS3_PR2_LAT | Internal | LATCHED | NOT_LATCHED | 13.4 |
|
|
|
| RS3 | - | RS3_SRCH_TMR_ACTV | Internal | ACTIVE | NOT_ACTIVE | 13.5 |
|
|
|
| RS3 | - | RS3A_GT_CLS_ILCK | Internal | CLOSED | NOT_CLOSED | 13.6 |
|
|
|
| RS3 | - | RS3_All_GTS_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 13.7 |
|
|
|
| RS3 | - | RS3_DIB_ACTV | Internal | ACTIVE | NOT_ACTIVE | 14 |
|
|
|
| RS3 | - | RS3_SRCH_SET_LAT | Internal | LATCHED | NOT_LATCHED | 14.1 |
|
|
|
| RS3 | - | RS3_All_GTS_DRS_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 14.2 |
|
|
|
| RS3 | - | RS3_911_PR1_LAT | Internal | LATCHED | NOT_LATCHED | 14.3 |
|
|
|
| RS3 | - | RS3_911_PR2_LAT | Internal | LATCHED | NOT_LATCHED | 14.4 |
|
|
|
| RS3 | - | RS3_911_DIB_ACTV | Internal | ACTIVE | NOT_ACTIVE | 14.5 |
|
|
|
| RS3 | - | RS3_911_PRSVD_SRCH | Internal | SET | NOT_SET | 14.6 |
|
|
|
| RS3 | - | RS3_911_EDR_CLS_ILCK | Internal | CLOSED | NOT_CLOSED | 14.7 |
|
|
|
| RS3 | - | RS3_911_EDR_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 15 |
|
|
|
| RS3 | - | RS3A_GT_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 15.1 |
|
|
|
| RS3 | - | RS3B_GT_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 15.2 |
|
|
|
| RS3 | - | RS3C_GT_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 15.3 |
|
|
|
| RS4 | - | RS4_PR1_LAT | Internal | LATCHED | NOT_LATCHED | 15.4 |
|
|
|
| RS4 | - | RS4_PR2_LAT | Internal | LATCHED | NOT_LATCHED | 15.5 |
|
|
|
| RS4 | - | RS4_SRCH_TMR_ACTV | Internal | ACTIVE | NOT_ACTIVE | 15.6 |
|
|
|
| RS4 | - | RS4A_GT_CLS_ILCK | Internal | CLOSED | NOT_CLOSED | 15.7 |
|
|
|
| RS4 | - | RS4_All_GTS_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 16 |
|
|
|
| RS4 | - | RS4_DIB_ACTV | Internal | ACTIVE | NOT_ACTIVE | 16.1 |
|
|
|
| RS4 | - | RS4_SRCH_SET_LAT | Internal | LATCHED | NOT_LATCHED | 16.2 |
|
|
|
| RS4 | - | RS4_All_GTS_DRS_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 16.3 |
|
|
|
| RS4 | - | RS4_912_PR1_LAT | Internal | LATCHED | NOT_LATCHED | 16.4 |
|
|
|
| RS4 | - | RS4_912_PR2_LAT | Internal | LATCHED | NOT_LATCHED | 16.5 |
|
|
|
| RS4 | - | RS4_912_DIB ACTV | Internal | ACTIVE | NOT_ACTIVE | 16.6 |
|
|
|
| RS4 | - | RS4_912_PRSVD_SRCH | Internal | SET | NOT_SET | 16.7 |
|
|
|
| RS4 | - | RS4_912_WDR_CLS_ILCK | Internal | CLOSED | NOT_CLOSED | 17 |
|
|
|
| RS4 | - | RS4_912_WDR_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 17.1 |
|
|
|
| RS4 | - | RS4A_GT_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 17.2 |
|
|
|
| RS4 | - | RS4B_GT_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 17.3 |
|
|
|
| RS4 | - | RS4C_GT_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 17.4 |
|
|
|
| RS5 | - | RS5_PR1_LAT | Internal | LATCHED | NOT_LATCHED | 17.5 |
|
|
|
| RS5 | - | RS5_PR2_LAT | Internal | LATCHED | NOT_LATCHED | 17.6 |
|
|
|
| RS5 | - | RS5_SRCH_TMR_ACTV | Internal | ACTIVE | NOT_ACTIVE | 17.7 |
|
|
|
| RS5 | - | RS5A_GT_CLS_ILCK | Internal | CLOSED | NOT_CLOSED | 18 |
|
|
|
| RS5 | - | RS5_All_GTS_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 18.1 |
|
|
|
| RS5 | - | RS5_DIB_ACTV | Internal | ACTIVE | NOT_ACTIVE | 18.2 |
|
|
|
| RS5 | - | RS5_SRCH_SET_LAT | Internal | LATCHED | NOT_LATCHED | 18.3 |
|
|
|
| RS5 | - | RS5_All_GTS_DRS_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 18.4 |
|
|
|
| RS5 | - | RS5_913_PR1_LAT | Internal | LATCHED | NOT_LATCHED | 18.5 |
|
|
|
| RS5 | - | RS5_913_PR2_LAT | Internal | LATCHED | NOT_LATCHED | 18.6 |
|
|
|
| RS5 | - | RS5_913_DIB ACTV | Internal | ACTIVE | NOT_ACTIVE | 18.7 |
|
|
|
| RS5 | - | RS5_913_PRSVD_SRCH | Internal | SET | NOT_SET | 19 |
|
|
|
| RS5 | - | RS5_913_WDR_CLS_ILCK | Internal | CLOSED | NOT_CLOSED | 19.1 |
|
|
|
| RS5 | - | RS5_913_All_DRS_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 19.2 |
|
|
|
| RS5 | - | RS5_913_SDR_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 19.3 |
|
|
|
| RS5 | - | RS5_913_WDR_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 19.4 |
|
|
|
| RS5 | - | RS5A_GT_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 19.5 |
|
|
|
| RS5 | - | RS5B_GT_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 19.6 |
|
|
|
| RS5 | - | RS5C_GT_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 19.7 |
|
|
|
| RS5 | - | RS5DE_GT_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 20 |
|
|
|
| RSY | - | KYBNK_N_CMPLT_LAT | Internal | LATCHED | NOT_LATCHED | 20.1 |
|
|
|
| RSY | - | KYBNK_S_CMPLT_LAT | Internal | LATCHED | NOT_LATCHED | 20.2 |
|
|
|
| RSY | - | ALL_KYBNK_CMPLT_LAT | Internal | LATCHED | NOT_LATCHED | 20.3 |
|
|
|
| RSY | - | RSY_ZN_CLS_LAT | Internal | LATCHED | NOT_LATCHED | 20.4 |
|
|
|
| RSY | - | ILCKS_CMPLT | Internal | LATCHED | NOT_LATCHED | 20.5 |
|
|
|
| RSY | - | RSY_SRCHD | Internal | SEARCHED | NOT SEARCHED | 20.6 |
|
|
|
| RSY | - | PERMITTED_ACCESS | Internal | SET | NOT_SET | 20.7 |
|
|
|
| RSY | - | NO_ACCESS | Internal | SET | NOT_SET | 21 |
|
|
|
| RSY | - | AV_WARN | Internal | ACTIVE | NOT ACTIVE | 21.1 |
|
|
|
| RSY | - | AV_WARN_CMPLT | Internal | SET | NOT_SET | 21.2 |
|
|
|
| RSY | Interface | RSY_SECURE | Internal | SET | NOT_SET | 21.3 |
|
|
|
| RSY | spare | spare | spare | spare | spare | 21.4 |
|
|
|
| RSY | SoftButton | EPICS_ILCK_SET_BTN | External | ACTIVE | NOT_ACTIVE |
| 23.1 |
|
|
| RSY | SoftButton | EPICS_KYBNK_N_REL_BTN | External | ACTIVE | NOT_ACTIVE |
| 23.2 |
|
|
| RSY | SoftButton | EPICS_KYBNK_S_REL_BTN | External | ACTIVE | NOT_ACTIVE |
| 23.3 |
|
|
| RSY | SoftButton | EPICS_PERMITTED_ACCESS_BTN | External | ACTIVE | NOT_ACTIVE |
| 23.4 |
|
|
| RSY | SoftButton | EPICS_NO_ACCESS_BTN | External | ACTIVE | NOT_ACTIVE |
| 23.5 |
|
|
| RSY | SoftButton | EPICS_RS1_SRCH_SET_BTN | External | ACTIVE | NOT_ACTIVE |
| 23.6 |
|
|
| RSY | SoftButton | EPICS_RS2_SRCH_SET_BTN | External | ACTIVE | NOT_ACTIVE |
| 23.7 |
|
|
| RSY | SoftButton | EPICS_RS3_SRCH_SET_BTN | External | ACTIVE | NOT_ACTIVE |
| 24 |
|
|
| RSY | SoftButton | EPICS_RS4_SRCH_SET_BTN | External | ACTIVE | NOT_ACTIVE |
| 24.1 |
|
|
| RSY | SoftButton | EPICS_RS5_SRCH_SET_BTN | External | ACTIVE | NOT_ACTIVE |
| 24.2 |
|
|
| RSY | SoftButton | EPICS_RT1_SRCH_SET_BTN | External | ACTIVE | NOT_ACTIVE |
| 24.3 |
|
|
| RSY | DryContact | EPICS_B209_UPS_24VDC_STAT_RT | input | OK | FAULT | 21.5 |
|
|
|
| RSY | DryContact | EPICS_B209_UPS_24VDC_STAT_LAT | Internal | LATCHED | NOT_LATCHED | 21.6 |
|
|
DC:Status |
| RSY | DryContact | EPICS_B209_UPS_DC_OK_LAT | Internal | LATCHED | NOT_LATCHED | 21.7 |
|
|
PLC:B209:1:DC:UpsFaultStatus |
| RSY | DryContact | EPICs_B209_UPS_ALARM_LAT | Internal | LATCHED | NOT_LATCHED | 22 |
|
|
|
| RSY | DryContact | EPICS_B209_UPS_BATT_MODE_LAT | Internal | LATCHED | NOT_LATCHED | 22.1 |
|
|
|
| RSY | DryContact | EPICS_B209_UPS_BATT_CHARGE_LAT | Internal | LATCHED | NOT_LATCHED | 22.2 |
|
|
|
| RSY | DryContact | EPICS_B913_UPS_24VDC_STAT_RT | input | OK | FAULT | 22.3 |
|
|
|
| RSY | DryContact | EPICS_B913_UPS_24VDC_STAT_LAT | Internal | LATCHED | NOT_LATCHED | 22.4 |
|
|
DC:Status |
| RSY | DryContact | EPICS_B913_UPS_DC_OK_LAT | Internal | LATCHED | NOT_LATCHED | 22.5 |
|
|
PLC:B209:1:DC:UpsFaultStatus |
| RSY | DryContact | EPICs_B913_UPS_ALARM_LAT | Internal | LATCHED | NOT_LATCHED | 22.6 |
|
|
|
| RSY | DryContact | EPICS_B913_UPS_BATT_MODE_LAT | Internal | LATCHED | NOT_LATCHED | 22.7 |
|
|
|
| RSY | DryContact | EPICS_B913_UPS_BATT_CHARGE_LAT | Internal | LATCHED | NOT_LATCHED | 23 |
|
|
|
| RSY | F-Sig | SAFETY_CHECKSUM | internal | HEX | HEX | 30-37 |
|
|
|
|
| spare | spare | spare | spare | spare | 24.6-29.7 |
|
|