This PLC is used to control and monitor three bulk power supplies for MCORs. It can also reset MCOR crates. Below are the PLC control and monitor tags.
Analog Readbacks (Data type: REAL):
Description |
Tag Name |
PS1 SETPOINT IN |
FLOATING_VALUES[1] |
PS2 SETPOINT IN |
FLOATING_VALUES[2] |
PS3 SETPOINT IN |
FLOATING_VALUES[3] |
PS1 SETPOINT OUT |
FLOATING_VALUES[11] |
PS2 SETPOINT OUT |
FLOATING_VALUES[12] |
PS3 SETPOINT OUT |
FLOATING_VALUES[13] |
PS1 OUTPUT VOLTAGE |
FLOATING_VALUES[21] |
PS2 OUTPUT VOLTAGE |
FLOATING_VALUES[22] |
PS3 OUTPUT VOLTAGE |
FLOATING_VALUES[23] |
PS1 GROUND CURRENT |
FLOATING_VALUES[31] |
PS2 GROUND CURRENT |
FLOATING_VALUES[32] |
PS3 GROUND CURRENT |
FLOATING_VALUES[33] |
Control Bits (Data Type: DINT):
Description |
Tag Name |
MCOR RESET 1 |
REMOTE_CONTROL[0].3 |
MCOR RESET 2 |
REMOTE_CONTROL[0].4 |
MCOR RESET 3 |
REMOTE_CONTROL[0].5 |
FAULT RESET REMOTE |
REMOTE_CONTROL[0].6 |
PS1 ON OFF REMOTE |
REMOTE_CONTROL[1].1 |
PS2 ON OFF REMOTE |
REMOTE_CONTROL[2].1 |
PS3 ON OFF REMOTE |
REMOTE_CONTROL[3].1 |
Status Bits (Data Type: DINT):
Description |
Tag Name |
FLOW SWITCH 1 FAULT STAT |
STATUS_BITS[0].1 |
FLOW SWITCH 2 FAULT STAT |
STATUS_BITS[0].2 |
PS1 GROUND FAULT STAT |
STATUS_BITS[1].0 |
PS1 OVERVOLTAGE STAT |
STATUS_BITS[1].1 |
PS1 UNDERVOLTAGE STAT |
STATUS_BITS[1].2 |
PS1 ON OFF STAT |
STATUS_BITS[1].3 |
PS1 REMOTE/LOCAL MODE STAT |
STATUS_BITS[1].4 |
PS1 RAMPING STAT |
STATUS_BITS[1].5 |
PS2 GROUND FAULT STAT |
STATUS_BITS[2].0 |
PS2 OVERVOLTAGE STAT |
STATUS_BITS[2].1 |
PS2 UNDERVOLTAGE STAT |
STATUS_BITS[2].2 |
PS2 ON OFF STAT |
STATUS_BITS[2].3 |
PS2 REMOTE/LOCAL MODE STAT |
STATUS_BITS[2].4 |
PS2 RAMPING STAT |
STATUS_BITS[2].5 |
PS3 GROUND FAULT STAT |
STATUS_BITS[3].0 |
PS3 OVERVOLATE STAT |
STATUS_BITS[3].1 |
PS3 UNDERVOLTAGE STAT |
STATUS_BITS[3].2 |
PS3 ON OFF STAT |
STATUS_BITS[3].3 |
PS3 REMOTE/LOCAL MODE STAT |
STATUS_BITS[3].4 |
PS3 RAMPING STAT |
STATUS_BITS[3].5 |
Note: The ".#" at the end of the tag signifies the bit in the tag used. For example, to reset MCOR 1, you would momentarily set REMOTE_CONTROL[0], bit 3 high. To monitor for a Flow Switch 1 fault, you would monitor bit 1 of STATUS_BITS[0].