Following the naming convention format of DeviceType:Area:Position:[instance:]Attribute

Each of the main rooms of the cryoplant building (East and West compressor rooms an cold box room) has two Oxygraf devices (East side and West side) with 4 channels each (0 to 3).

Device type: ODM

Area:

  • CR1 for cryoplant 1 a.k.a. West cryoplant room
  • CR0 for the cold box room
  • CR2 for cryoplant 2 a.k.a. East cryoplant room

Position:

  • W for West side of the area
  • E for East side of the area

Instance:

  • 0 for Channel 0
  • 1 for Channel 1
  • 2 for Channel 2
  • 3 for Channel 3

Full PV names mapped to PLC channels

Commands

Label PV name

Ladder Logic

Name

PLC's Type:

EPICS Bit

Offset

Logic 0

State Name

Logic 1

State Name

Logic 0

Alarm

Logic 1

Alarm

WCR West Oxigraf DisableODM:CR1:1:SET_OXGF_DISABLEa0.i0input, virtual7NOT_DISABLEDISABLENO_ALARMNO_ALARM
WCR West Oxigraf EnableODM:CR1:1:SET_OXGF_ENABLEa0.i1input, virtual6NOT_ENABLEENABLENO_ALARMNO_ALARM
WCR East Oxigraf DisableODM:CR1:2:SET_OXGF_DISABLEa0.i2input, virtual5NOT_DISABLEDISABLENO_ALARMNO_ALARM
WCR East Oxigraf EnableODM:CR1:2:SET_OXGF_ENABLEa0.i3input, virtual4NOT_ENABLEENABLENO_ALARMNO_ALARM
CBR West Oxigraf DisableODM:CR0:1:SET_OXGF_DISABLEa0.i4input, virtual3NOT_DISABLEDISABLENO_ALARMNO_ALARM
CBR West Oxigraf EnableODM:CR0:1:SET_OXGF_ENABLEa0.i5 input, virtual2NOT_ENABLEENABLENO_ALARMNO_ALARM
CBR East Oxigraf DisableODM:CR0:2:SET_OXGF_DISABLEa0.i6 input, virtual1NOT_DISABLEDISABLENO_ALARMNO_ALARM
CBR East Oxigraf EnableODM:CR0:2:SET_OXGF_ENABLEa0.i7input, virtual0NOT_ENABLEENABLENO_ALARMNO_ALARM
ECR West Oxigraf DisableODM:CR2:1:SET_OXGF_DISABLEa0.i8input, virtual15NOT_DISABLEDISABLENO_ALARMNO_ALARM
ECR West Oxigraf EnableODM:CR2:1:SET_OXGF_ENABLEa0.i9input, virtual14NOT_ENABLEENABLENO_ALARMNO_ALARM
ECR East OxigrafDisableODM:CR2:2:SET_OXGF_DISABLEa0.i10input, virtual13NOT_DISABLEDISABLENO_ALARMNO_ALARM
ECR East Oxigraf EnableODM:CR2:2:SET_OXGF_ENABLEa0.i11input, virtual12NOT_ENABLEENABLENO_ALARMNO_ALARM
WCR Alarm BypassODM:CR1:SET_AL_BYPASSa0.i12input, virtual11NOT_BYPASSBYPASSNO_ALARM

NO_ALARM

WCR Alarm UnbypassODM:CR1:SET_AL_UNBYPASSa0.i13input, virtual10NOT_UNBYPASSUNBYPASSNO_ALARMNO_ALARM
WCR Alarm MuteODM:CR1:SET_AL_MUTEa0.i14input, virtual9NOT_MUTEMUTENO_ALARMNO_ALARM
WCR Alarm UnmuteODM:CR1:SET_AL_UNMUTEa0.i15input, virtual8NOT_UNMUTEUNMUTENO_ALARMNO_ALARM
CBR Alarm BypassODM:CR0:SET_AL_BYPASSa0.i16input, virtual23NOT_BYPASSBYPASSNO_ALARM

NO_ALARM

CBR Alarm UnbypassODM:CR0:SET_AL_UNBYPASSa0.i17input, virtual22NOT_UNBYPASSUNBYPASSNO_ALARMNO_ALARM
CBR Alarm MuteODM:CR0:SET_AL_MUTEa0.i18input, virtual21NOT_MUTEMUTENO_ALARMNO_ALARM
CBR Alarm UnmuteODM:CR0:SET_AL_UNMUTEa0.i19input, virtual20NOT_UNMUTEUNMUTENO_ALARMNO_ALARM
ECR Alarm BypassODM:CR2:SET_AL_BYPASSa0.i20input, virtual19NOT_BYPASSBYPASSNO_ALARM

NO_ALARM

ECR Alarm UnbypassODM:CR2:SET_AL_UNBYPASSa0.i21input, virtual18NOT_UNBYPASSUNBYPASSNO_ALARMNO_ALARM
ECR Alarm MuteODM:CR2:SET_AL_MUTEa0.i22input, virtual17NOT_MUTEMUTENO_ALARMNO_ALARM
ECR Alarm UnmuteODM:CR2:SET_AL_UNMUTEa0.i23input, virtual16NOT_UNMUTEUNMUTENO_ALARMNO_ALARM
Alarm ResetODM:CR00:SET_AL_RESETa0.i24input, virtual31NOT_RESETRESETNO_ALARMNO_ALARM
WCR Fan ForceODM:CR1:SET_FAN_FORCEa0.i25input, virtual30NOT_FAN_FORCEFAN_FORCENO_ALARMNO_ALARM
WCR Fan UnforceODM:CR1:SET_FAN_UNFORCEa0.i26input, virtual29NOT_FAN_UNFORCEFAN_UNFORCENO_ALARMNO_ALARM
CBR Fan ForceODM:CR0:SET_FAN_FORCEa0.i27input, virtual28NOT_FAN_FORCEFAN_FORCENO_ALARMNO_ALARM
CBR Fan UnforceODM:CR0:SET_FAN_UNFORCEa0.i28input, virtual27NOT_FAN_UNFORCEFAN_UNFORCENO_ALARMNO_ALARM
ECR Fan ForceODM:CR2:SET_FAN_FORCEa0.i29input, virtual26NOT_FAN_FORCEFAN_FORCENO_ALARMNO_ALARM
ECR Fan UnforceODM:CR2:SET_FAN_UNFORCEa0.i30input, virtual25NOT_FAN_UNFORCEFAN_UNFORCENO_ALARMNO_ALARM

Readback

Label PV name

Ladder Logic

Name

PLC's Type:

EPICS Bit

Offset

Logic 0

State Name

Logic 1

State Name

Logic 0

Alarm

Logic 1

Alarm

WCR West Oxigraf Ch0 RealODM:CR1:1:FAULTa0.o0output, virtual7FAULTOKMAJORNO_ALARM
WCR West Oxigraf Ch0 LatchODM:CR1:1:FAULT_LTHa0.o1output, virtual6FAULTOKMAJORNO_ALARM
WCR West Oxigraf Ch1 RealODM:CR1:1:1:FAULTa0.o2output, virtual5FAULTOKMAJORNO_ALARM
WCR West Oxigraf Ch1 LatchODM:CR1:1:1:FAULT_LTHa0.o3output, virtual4FAULTOKMAJORNO_ALARM
WCR West Oxigraf Ch2 RealODM:CR1:1:2:FAULTa0.o4output, virtual3FAULTOKMAJORNO_ALARM
WCR West Oxigraf Ch2 LatchODM:CR1:1:2:FAULT_LTHa0.o5output, virtual2FAULTOKMAJORNO_ALARM
WCR West Oxigraf Ch3 RealODM:CR1:1:3:FAULTa0.o6output, virtual1FAULTOKMAJORNO_ALARM
WCR West Oxigraf Ch3 LatchODM:CR1:1:3:FAULT_LTHa0.o7output, virtual0FAULTOKMAJORNO_ALARM
WCR East Oxigraf Ch0 RealODM:CR1:2:FAULTa0.o8output, virtual15FAULTOKMAJORNO_ALARM
WCR East Oxigraf Ch0 LatchODM:CR1:2:FAULT_LTHa0.o9output, virtual14FAULTOKMAJORNO_ALARM
WCR East Oxigraf Ch1 RealODM:CR1:2:1:FAULTa0.o10output, virtual13FAULTOKMAJORNO_ALARM
WCR East Oxigraf Ch1 LatchODM:CR1:2:1:FAULT_LTHa0.o11output, virtual12FAULTOKMAJORNO_ALARM
WCR East Oxigraf Ch2 RealODM:CR1:2:2:FAULTa0.o12output, virtual11FAULTOKMAJORNO_ALARM
WCR East Oxigraf Ch2 LatchODM:CR1:2:2:FAULT_LTHa0.o13output, virtual10FAULTOKMAJORNO_ALARM
WCR East Oxigraf Ch3 RealODM:CR1:2:3:FAULTa0.o14output, virtual9FAULTOKMAJORNO_ALARM
WCR East Oxigraf Ch3 LatchODM:CR1:2:3:FAULT_LTHa0.o15output, virtual8FAULTOKMAJORNO_ALARM
WCR West Sys OK RealODM:CR1:1:SYS_OKa0.o16output, virtual23FAULTOKMAJORNO_ALARM
WCR West Sys OK LatchODM:CR1:1:SYS_OK_LTHa0.o17output, virtual22FAULTOKMAJORNO_ALARM
WCR East Sys OK RealODM:CR1:2:SYS_OKa0.o18output, virtual21FAULTOKMAJORNO_ALARM
WCR East Sys OK LatchODM:CR1:2:SYS_OK_LTHa0.o19output, virtual20FAULTOKMAJORNO_ALARM
CBR West Oxigraf Ch0 RealODM:CR0:1:FAULTa0.o20output, virtual19FAULTOKMAJORNO_ALARM
CBR West Oxigraf Ch0 LatchODM:CR0:1:FAULT_LTHa0.o21output, virtual18FAULTOKMAJORNO_ALARM
CBR West Oxigraf Ch1 RealODM:CR0:1:1:FAULTa0.o22output, virtual17FAULTOKMAJORNO_ALARM
CBR West Oxigraf Ch1 LatchODM:CR0:1:1:FAULT_LTHa0.o23output, virtual16FAULTOKMAJORNO_ALARM
CBR West Oxigraf Ch2 RealODM:CR0:1:2:FAULTa0.o64output, virtual95FAULTOKMAJORNO_ALARM
CBR West Oxigraf Ch2 LatchODM:CR0:1:2:FAULT_LTHa0.o65output, virtual94FAULTOKMAJORNO_ALARM
CBR West Oxigraf Ch3 RealODM:CR0:1:3:FAULTa0.o66output, virtual93FAULTOKMAJORNO_ALARM
CBR West Oxigraf Ch3 LatchODM:CR0:1:3:FAULT_LTHa0.o67output, virtual92FAULTOKMAJORNO_ALARM
CBR East Oxigraf Ch0 RealODM:CR0:2:FAULTa0.o68output, virtual91FAULTOKMAJORNO_ALARM
CBR East Oxigraf Ch0 LatchODM:CR0:2:FAULT_LTHa0.o69output, virtual90FAULTOKMAJORNO_ALARM
CBR East Oxigraf Ch1 RealODM:CR0:2:1:FAULTa0.o70output, virtual89FAULTOKMAJORNO_ALARM
CBR East Oxigraf Ch1 LatchODM:CR0:2:1:FAULT_LTHa0.o71output, virtual88FAULTOKMAJORNO_ALARM
CBR East Oxigraf Ch2 RealODM:CR0:2:2:FAULTa0.o72output, virtual103FAULTOKMAJORNO_ALARM
CBR East Oxigraf Ch2 LatchODM:CR0:2:2:FAULT_LTHa0.o73output, virtual102FAULTOKMAJORNO_ALARM
CBR East Oxigraf Ch3 RealODM:CR0:2:3:FAULTa0.o74output, virtual101FAULTOKMAJORNO_ALARM
CBR East Oxigraf Ch3 LatchODM:CR0:2:3:FAULT_LTHa0.o75output, virtual100FAULTOKMAJORNO_ALARM
CBR West Sys OK RealODM:CR0:1:SYS_OKa0.o76output, virtual99FAULTOKMAJORNO_ALARM
CBR West Sys OK LatchODM:CR0:1:SYS_OK_LTHa0.o77output, virtual98FAULTOKMAJORNO_ALARM
CBR East Sys OK RealODM:CR0:2:SYS_OKa0.o78output, virtual97FAULTOKMAJORNO_ALARM
CBR East Sys OK LatchODM:CR0:2:SYS_OK_LTHa0.o79output, virtual96FAULTOKMAJORNO_ALARM
ECR West Oxigraf Ch0 RealODM:CR2:1:FAULTa0.o80output, virtual111FAULTOKMAJORNO_ALARM
ECR West Oxigraf Ch0 LatchODM:CR2:1:FAULT_LTHa0.o81output, virtual110FAULTOKMAJORNO_ALARM
ECR West Oxigraf Ch1 RealODM:CR2:1:1:FAULTa0.o82output, virtual109FAULTOKMAJORNO_ALARM
ECR West Oxigraf Ch1 LatchODM:CR2:1:1:FAULT_LTHa0.o83output, virtual108FAULTOKMAJORNO_ALARM
ECR West Oxigraf Ch2 RealODM:CR2:1:2:FAULTa0.o84output, virtual107FAULTOKMAJORNO_ALARM
ECR West Oxigraf Ch2 LatchODM:CR2:1:2:FAULT_LTHa0.o85output, virtual106FAULTOKMAJORNO_ALARM
ECR West Oxigraf Ch3 RealODM:CR2:1:3:FAULTa0.o86output, virtual105FAULTOKMAJORNO_ALARM
ECR West Oxigraf Ch3 LatchODM:CR2:1:3:FAULT_LTHa0.o87output, virtual104FAULTOKMAJORNO_ALARM
ECR East Oxigraf Ch0 RealODM:CR2:2:FAULTa0.o88output, virtual119FAULTOKMAJORNO_ALARM
ECR East Oxigraf Ch0 LatchODM:CR2:2:FAULT_LTHa0.o89output, virtual118FAULTOKMAJORNO_ALARM
ECR East Oxigraf Ch1 RealODM:CR2:2:1:FAULTa0.o90output, virtual117FAULTOKMAJORNO_ALARM
ECR East Oxigraf Ch1 LatchODM:CR2:2:1:FAULT_LTHa0.o91output, virtual116FAULTOKMAJORNO_ALARM
ECR East Oxigraf Ch2 RealODM:CR2:2:2:FAULTa0.o92output, virtual115FAULTOKMAJORNO_ALARM
ECR East Oxigraf Ch2 LatchODM:CR2:2:2:FAULT_LTHa0.o93output, virtual114FAULTOKMAJORNO_ALARM
ECR East Oxigraf Ch3 RealODM:CR2:2:3:FAULTa0.o94output, virtual113FAULTOKMAJORNO_ALARM
ECR East Oxigraf Ch3 LatchODM:CR2:2:3:FAULT_LTHa0.o95output, virtual112FAULTOKMAJORNO_ALARM
ECR West Sys OK RealODM:CR2:1:SYS_OKa0.o96output, virtual127FAULTOKMAJORNO_ALARM
ECR West Sys OK LatchODM:CR2:1:SYS_OK_LTHa0.o97output, virtual126FAULTOKMAJORNO_ALARM
ECR East Sys OK RealODM:CR2:2:SYS_OKa0.o98output, virtual125FAULTOKMAJORNO_ALARM
ECR East Sys OK LatchODM:CR2:2:SYS_OK_LTHa0.o99output, virtual124FAULTOKMAJORNO_ALARM
WCR Alarm BypassODM:CR1:AL_BYPASSEDa0.o100output, virtual123BYPASSEDNOT_BYPASSEDMINORNO_ALARM
WCR Alarm MuteODM:CR1:AL_MUTEDa0.o101output, virtual122MUTEDNOT_MUTEDMINORNO_ALARM
WCR Strobe OutODM:CR1:STROBEa0.o102output, virtual121STROBE_ONSTROBE_OFFNO_ALARMNO_ALARM
WCR Horn OutODM:CR1:HORNa0.o103output, virtual120HORN_ONHORN_OFFNO_ALARMNO_ALARM
WCR Fan OutODM:CR1:FANa0.o104output, virtual135FAN_OFFFAN_ONNO_ALARMNO_ALARM
WCR West Oxigraf DisableODM:CR1:1:OXGF_DISABLEDa0.o106output, virtual133DISABLEDENABLEDMINORNO_ALARM
WCR East Oxigraf DisableODM:CR1:2:OXGF_DISABLEDa0.o107output, virtual132DISABLEDENABLEDMINORNO_ALARM
CBR Alarm BypassODM:CR0:AL_BYPASSEDa0.o108output, virtual132BYPASSEDNOT_BYPASSEDMINORNO_ALARM
CBR Alarm MuteODM:CR0:AL_MUTEDa0.o109output, virtual131MUTEDNOT_MUTEDMINORNO_ALARM
CBR Strobe OutODM:CR0:STROBEa0.o110output, virtual130STROBE_ONSTROBE_OFFNO_ALARMNO_ALARM
CBR Horn OutODM:CR0:HORNa0.o111output, virtual129HORN_ONHORN_OFFNO_ALARMNO_ALARM
CBR Fan OutODM:CR0:FANa0.o112output, virtual143FAN_OFFFAN_ONNO_ALARMNO_ALARM
CBR West Oxigraf DisableODM:CR0:1:OXGF_DISABLEa0.o114output, virtual141DISABLEDENABLEDMINORNO_ALARM
CBR East Oxigraf DisableODM:CR0:2:OXGF_DISABLEa0.o115output, virtual140DISABLEDENABLEDMINORNO_ALARM
ECR Alarm BypassODM:CR2:AL_BYPASSa0.o116output, virtual139BYPASSEDNOT_BYPASSEDMINORNO_ALARM
ECR Alarm MuteODM:CR2:AL_MUTEa0.o117output, virtual138MUTEDNOT_MUTEDMINORNO_ALARM
ECR Strobe OutODM:CR2:STROBEa0.o118output, virtual137STROBE_ONSTROBE_OFFNO_ALARMNO_ALARM
ECR Horn OutODM:CR2:HORNa0.o119output, virtual136HORN_ONHORN_OFFNO_ALARMNO_ALARM
ECR Fan OutODM:CR2:FANa0.o120output, virtual151FAN_OFFFAN_ONNO_ALARMNO_ALARM
ECR West Oxigraf DisableODM:CR2:1:OXGF_DISABLEa0.o122output, virtual149DISABLEDENABLEDMINORNO_ALARM
ECR East Oxigraf DisableODM:CR2:2:OXGF_DISABLEa0.o123output, virtual148DISABLEDENABLEDMINORNO_ALARM
Yellow AlarmODM:CR00:YELLOW_ALARMa0.o124output, virtual147YELLOW_ALARMNO_YELLOW_ALARMMINORNO_ALARM
Red AlarmODM:CR00:RED_ALARMa0.o125output, virtual146RED_ALARMNO_RED_ALARMMAJORNO_ALARM
  • No labels