Reference:

Gun Buncher EPS block diagram : G-B Block Diag PDF.pdf

 

These PV`s are read from Gun LCLS2 AND Gate
PV_NAMEDESC
GUN:GUNB:100:ANDGATE:BYPALLBypass all signals on LCLS2 GUNB AND GATE
GUN:GUNB:100:ANDGATE:SSA1BYPGun SSA #1  Bypass signal
GUN:GUNB:100:ANDGATE:SSA2BYPGun SSA #2  Bypass signal
GUN:GUNB:100:ANDGATE:ARCDETSUMBYPGun circulator Arc detector - bypass 
GUN:GUNB:100:ANDGATE:BCSSUMBYPBCS A-B status bypass
GUN:GUNB:100:ANDGATE:EPSSUMBYPGUN EPS status bypass
GUN:GUNB:100:ANDGATE:RFS1BYPGun RFS #1 Interlock bypass
GUN:GUNB:100:ANDGATE:RFS2BYPGun RFS #2 Interlock bypass
GUN:GUNB:100:ANDGATE:SSA1Gun SSA #1  Status signal
GUN:GUNB:100:ANDGATE:SSA2Gun SSA #2  Status signal
GUN:GUNB:100:ANDGATE:ARCDETSUMGun circulator Arc detector - Status (both gun and   buncher) 
GUN:GUNB:100:ANDGATE:BCSSUMBCS A-B status Status
GUN:GUNB:100:ANDGATE:EPSSUMEPS status Status
GUN:GUNB:100:ANDGATE:RFS1Gun RFS #1 Interlock Status
GUN:GUNB:100:ANDGATE:RFS2Gun RFS #2 Interlock Status
GUN:GUNB:100:ANDGATE:SUMShort gate status - sum of all 8 signals ; TTL signal
These PV`s are read   from Arc Detector Level Shifter
GUN:GUNB:100:ARCDET_CAV1Gun Cavity #1
GUN:GUNB:100:ARCDET_CAV2Gun Cavity #2
GUN:GUNB:100:ARCDET_WNDW1Gun RF Windiow
GUN:GUNB:100:ARCDET_WNDW2Gun RF Window
ACCL:GUNB:455:ARCDET_CAV1Bunch  Cavity #1
These PV`s are read from BUNCHER LCLS2 AND GATE
ACCL:GUNB:455:ANDGATE:BYPALLBypass all signals on this gate
ACCL:GUNB:455:ANDGATE:SSA1BYPBuncher SSA #1  Bypass signal
ACCL:GUNB:455:ANDGATE:SSA2BYPBuncher SSA #2  Bypass signal
ACCL:GUNB:455:ANDGATE:SSA3BYPBuncher SSA #3  Bypass signal
ACCL:GUNB:455:ANDGATE:SSA4BYPBuncher SSA #4  Bypass signal
ACCL:GUNB:455:ANDGATE:EPSSUMBYPEPS status bypass
ACCL:GUNB:455:ANDGATE:RFS1BYPBuncher RFS #1 Interlock bypass
ACCL:GUNB:455:ANDGATE:RFS2BYPBuncher RFS #2 Interlock bypass
ACCL:GUNB:455:ANDGATE:SSA1Buncher SSA #3  Status signal
ACCL:GUNB:455:ANDGATE:SSA2Buncher SSA #4  Status signal
ACCL:GUNB:455:ANDGATE:SSA3Buncher SSA #5  Status signal
ACCL:GUNB:455:ANDGATE:SSA4Buncher SSA #6  Status signal
ACCL:GUNB:455:ANDGATE:EPSSUMEPS status Status
ACCL:GUNB:455:ANDGATE:RFS1Buncher RFS #1 Interlock Status
ACCL:GUNB:455:ANDGATE:RFS2Buncher RFS #2 Interlock Status
ACCL:GUNB:455:ANDGATE:SUM Short gate status - sum of all 8 signals ; TTL signal
These PV`s are read from gun circulator
GUN:GUNB:100:CIRC1MODEGun circulator 1  manual/auto 
GUN:GUNB:100:CIRC1STATGun circulator 1 ok/fault 
GUN:GUNB:100:CIRC2MODEGun circulator 2 manual/auto 
GUN:GUNB:100:CIRC2STATGun circulator 2 ok/fault 
GUN:GUNB:100:ARCDET_CIRC1DET1Gun circulator 1 arc detector 1 status
GUN:GUNB:100:ARCDET_CIRC1DET2Gun circulator 1 arc detector 2 status
GUN:GUNB:100:ARCDET_CIRC2DET1Gun circulator 2 arc detector 1 status
GUN:GUNB:100:ARCDET_CIRC2DET2Gun circulator 2 arc detector 2 status
GUN:GUNB:100:ARCDET_CIRC1SUMGun circulator 1, arc detector all status
GUN:GUNB:100:ARCDET_CIRC2SUMGun circulator 2, arc detector all status
These PV`s are read from buncher interlock IO
GUN:GUNB:100:INTLK:BCSCHABCS A enable
GUN:GUNB:100:INTLK:BCSCHBBCS B enable
These PV`s are read from arc detector level shifter
GUN:GUNB:100:ARCDET_SUMGun arc detector sum ok
ACCL:GUNB:455:ARCDET_SUMBunch arc detector sun ok
GUN:GUNB:100:ARCDET_CHASPWRGun arc detector power ok
ACCL:GUNB:455:ARCDET_CHASPWRBunch arc detector power ok
These PV`s are read from buncher interlock IO
GUN:GUNB:100:INTLK:BCSSUMGUN_RF_COAX_OK
GUN:GUNB:100:INTLK:RFENABLEGUN_RF_ENABLE
ACCL:GUNB:455:INTLK:RFENABLEBUN_RF_ENABLE
These PV`s are read from DO vacuum plc
GUN:GUNB:100:EPSVACSUMGun B vacuum ok
ACCL:GUNB:455:EPSVACSUMbuncher vacuum ok
These PV`s are test and reset controls for Arc Detector Level Shifter channel tests
GUN:GUNB:100:ARCDET_CAV1TESTGun Cavity1   
GUN:GUNB:100:ARCDET_CAV1RESET 
GUN:GUNB:100:ARCDET_CAV2TESTGun Cavity2
GUN:GUNB:100:ARCDET_CAV2RESET 
GUN:GUNB:100:ARCDET_WNDW1TESTGun RF Window 
GUN:GUNB:100:ARCDET_WNDW1RESET 
GUN:GUNB:100:ARCDET_WNDW2TESTGun RF Window
GUN:GUNB:100:ARCDET_WNDW2RESET 
ACCL:GUNB:455:ARCDET_CAVTESTBuncher Cavity1
ACCL:GUNB:455:ARCDET_CAVRESET 
These PV`s are read from buncher interlock IO
GUN:GUNB:100:INTLK:EPSSUMEPS Enable, GUN Status OK- (J3)
ACCL:GUNB:455:INTLK:EPSSUMEPS Enable, BUN Status OK- (J3)
  • No labels