IP Address: 192.168.1.6

IP Address set on pc: 192.168.1.10

Subnet Mask: 255.255.252.0


Links to Beckhoff website:

EK900: https://www.beckhoff.com/en-us/products/i-o/ethercat-terminals/ekxxxx-bus-coupler/ek9000.html

EL5042: https://www.beckhoff.com/en-us/products/i-o/ethercat-terminals/el5xxx-position-measurement/el5042.html


  • Took a while, but connecting worked. web address is: 192.168.1.6/config (works with or without connecting to wifi)
  • If connecting from dev network, namrata used http://ek-602e17/config , on DHCP
  • DIP switched 9 and 10 set to 0 (to get IP address and not DHCP) , DIP switched 2 and 3 are at 1 to get 00000110 in binary, this equates to 6 in decimal.


Modbus:

  • Based on a master slave. Master sends request and slave responds with a response.
  • Modbus data can be carried on two channels - over serial communication, or over a network connection. This flexibility is part of the lasting appeal of Modbus.
  • There are two types of Modbus serial protocols, RS-232 and RS-485. Modbus RS-232 allows concurrent, full-duplex flow of data. Modbus RS-485 is half-duplex, and indicates values using differences in voltage.
  • Modbus messages can also be sent over Ethernet or TCP/IP. These Modbus messages are packed as a single bit, or 16-bit word packets.


Using ModBusPoll (app):

  • Connect on Modbus TCP/IP:
    • Address 192.168.1.6
  • (3) Read holding registers 


Using Modpoll (cmd lines):

  • cd into directory that has modpoll (modpoll-3.10/win). ./modpoll -h  to give you info 
  • Cmd line that gave me data, that data changes with encoder changes, but is signed, and switches between -ve and +ve:
    • First thing that worked: ./modpoll -m tcp -t 3:int 192.168.1.6  (this gives some encoder readback, since the address for data is 0x0000 (or 0x0001 bc modpoll is weird))
  • Another Cmd line:
    • ./modpoll -m tcp -t 3 -r 0x1120 -c 20 -1 192.168.1.6 
    • 16 bit response, hence -t 3  is used
    • -c 20  gives the 20 data after the address inclusive
    • -0  starts reference from 0 instead of 1 (when I do this, the output starts from the second register (which is hidden because it jumps between registers 0→2→4 etc) this gives better encoder readings because it's linear, but still not accurate)
    • ./modpoll -m tcp -t 3:int -0 -r 0x0001 -c 4 192.168.1.6 (cmd line that worked, we care about the first register, if you only want that data, get rid of the -c 4  

Switching encoder to the second terminal:

  • I believe register 6 is the one we care about, which is consistent with register 1 from previous terminal (1+5=6) 
  • For some reason it is almost exactly half the encoder counts of the previous one. 


Lines of Codes that work:

  • To get the encoder reading of the first encoder:
    • ./modpoll -m tcp -t 3:int -0 -r 0x0001 192.168.1.6
  • To get the encoder reading of the second encoder:
    • ./modpoll -m tcp -t 3:int -0 -r 0x0006 192.168.1.6