Ignore Logic
- Documentation
- Highlight new truth table state when selected
Mockup
======================================= Ignore Logic ===========================================
------------------------------------------------------------------------------------------------
Logic History
=========================< slider >============================================ |
[] Show Live |
------------------------------------------------------------------------------------------------
Ignore Logic Ignored Truth Tables
Sort 2 Sort 0 Sort 1 | Sort 1 Sort 0
============== =========== ======== | ================================ =================
Ignore Logic Is Ignoring Min Rate | Truth Table Min Rate
============== =========== ======== | ================================ =================
TD11 Is In Yes 0 Hz | BFW 1910 Position 0 Hz
TDUND Is In No 10 Hz | BCS LION753 Threshold 0 Hz
YG BL211 Is In No 60 Hz | BLM Pedestal Thresholds: UND 920 0 Hz
============== =========== ======== | Temperature: North Arc Summary 0 Hz
VVPG LI22 Position 0 Hz |
YAG IN20 211 Position 10 Hz |
PIC HVPS B912 10 Hz |
PIC HVPS B913 120 Hz |
================================ ================= |
-------------------------------------+-----------------------------------------------------
Name: YAG IN20 211 Position
Current State: Out
Solution: –
Contacts: –
====== = = ==================== ==================== ==================== ====================
Name B A Pockels Cell Mechanical Shutter BYKIK Laser Heater Shutter
====== = = ==================== ==================== ==================== ====================
Moving F F 0 Hz 0 Hz 0 Hz – Bypass to state
Out F T 120 Hz 120 Hz 120 Hz – Bypass to state -> window shows PVs and asks for bypass time
In T F 10 Hz 10 Hz 10 Hz – Bypass to state
Broken T T 0 Hz 0 Hz 0 Hz – Bypass to state
====== = = ==================== ==================== ==================== ====================
Where::
Note to sergei: Device name_Fault name from config db
A = (YG_BL211_OUT_LIMIT)_(STATE) as PV Name
B = (YG_BL211_IN_LIMIT)_(STATE) as PV Name
------------------------------------------------------------------------------------------------
Summary / Faults / Logic / Ignore Logic / History /
Bypass Dialog
- Let's drop the calendar view and simplify the interface.
- Default to 0 for all duration values.
- Show truth table name in the window's title bar
- Read-only values in table
- Allow tabbing between duration values
- Tab order: days -> hours -> minutes -> seconds -> days
- Initialize window with hours field selected