Production PV Gateways

A list of the various LCLS, LCLS-II, FACET, and Test Facilities gateways managed by EED Systems Group.

NamePurpose PVs served Host
CAS port
Beacon Port
Beacon sent to Document/CommentUpgrade Status
LCLS
gwEbeamServe

Serving LCLS PVs (Ebeam) to Photon

Readonly

Write for selected PVs

lcls-daemon350805081

172.21.40.63

(Photon Gateway Subnet)

Design

Admin

Allow all

Deny OTRS:DMP1:695:.*

  • Upgrade to 64-bit EPICS7  
gwEbeamServeWF

Serving LCLS PVs (Ebeam) to Photon

Readonly

Write for selected PVs

lcls-daemon350795081

172.21.40.63

(Photon Gateway Subnet)

Deny all

Allow OTRS:DMP1:695:.*

(dedicated to serve XTCAV OTRDMP camera image PV)

  • Upgrade to 64-bit EPICS7 
gwLCLS4FACETServing LCLS PVs to FACETReadonlylcls-daemon1050705069

172.27.75.255

(FACETCA)

Design

Admin

  • Upgrade to 64-bit EPICS7 
gwLCLS4LCLSIIServing LCLS PVs to LCLS-IIRead and Writelcls-daemon1050605069172.27.131.255 ( LCLS2IOC) and 172.27.11.255 (MCCSRV 
  • Upgrade to 64-bit EPICS7 
gwLCLSPUBServing LCLS PVs to publicReadonlylcls-prod0150685069

134.79.151.255

(DMZ)

Admin

  • Upgrade to 64-bit EPICS7 
gwLCLSARCH0Serving LCLS and LCLS-II PVs to Archiver on DMZReadonlylcls-prod0150765069

134.79.151.255

(DMZ)

.* ALLOW (default)

Deny a list

refer gwLCLSARCH*.dat

 

 

  • Upgrade to 64-bit EPICS7 
gwLCLSARCH1Serving LCLS and LCLS-II PVs to Archiver on DMZReadonlylcls-prod0150775069

134.79.151.255

(DMZ)

.* DENY

Allow portion in the list

refer gwLCLSARCH*.dat

  • Upgrade to 64-bit EPICS7 
gwLCLSARCH2Serving LCLS and LCLS-II PVs to Archiver on DMZReadonlylcls-prod0150785069

134.79.151.255

(DMZ)

.* DENY

Allow portion in the list

refer gwLCLSARCH*.dat

  • Upgrade to 64-bit EPICS7 
gwLCLSARCH3Serving LCLS and LCLS-II PVs to Archiver on DMZReadonlylcls-prod0150795069

134.79.151.255

(DMZ)

.* DENY

Allow portion in the list

refer gwLCLSARCH*.dat

  • Upgrade to 64-bit EPICS7 
LCLS-II
gwLCLSII4LCLSServing LCLS-II PVs to LCLSRead and Writelcls2-daemon1050605069172.27.3.255 ( LCLSIOC) and 172.27.11.255 (MCCSRV) 
  • Upgrade to 64-bit EPICS7 
FACET
gwFACET4LCLSServing FACET PVs to LCLSReadonlyfacet-daemon150705069

172.27.11.255

(LCLSCA)

Design

Admin

  • Upgrade to 64-bit EPICS7
gwFACETPUBServing FACET PVs to publicReadonlylcls-prod0150635069

134.79.151.255

(DMZ)

Design
  • Upgrade to 64-bit EPICS7 
gwEXP2FACETServing Fedora based PCOEdge Camera PVs in B244 to FACET controls

Readonly

Write allowed from facet-srv20 to slac-dev-fed

lcls-prod0150625069

facet-srv*:

172.27.72.28 172.27.72.22 172.27.72.23

Not in use currently
  • Upgrade to 64-bit EPICS7
gwFACETARCHServing FACET PVs to Archiver on DMZReadonlylcls-prod0150755069

134.79.151.255

(DMZ)

Allow all

 

  • Upgrade to 64-bit EPICS7 
Test Facilities
gwACCTESTPUBServing Test Facilities PV to publicReadonlytestfac-daemon250485049

134.79.219.255

(LCLSDEV)

doc
  • Upgrade to 64-bit EPICS7
Cryo
gwCRYO4LCLSServing Cryo PVs to LCLSRead and Writecryo-daemon150615069172.27.43.255 172.27.11.255 134.79.151.21

.* ALLOW

.* ALLOW CANWRITE

  • Upgrade to 64-bit EPICS7 

 

LCLS Gateway Test Procedures


lcls-daemon3

gwEbeamServe:

  1. Change /etc/init.d/st.gwEbeamServe on lcls-daemon3 to use CMDPATH=/usr/local/lcls/tools/gateway/script/st.gwEbeamServe64
  2. Restart gateway:

    [laci@lcls-daemon3]$ /etc/init.d/st.gwEbeamServe restart
  3. Verify that all LCLSIOC subnet PVs except for OTRS:DMP1:695:* PVs can be seen from Photon/PCDS subnet clients.
  4. Verify that the lclshome->Network (Global)->PV Gateway Diag->Ebeam Serve display is repopulated after the restart.
  5. Check /u1/lcls/tools/gateway/gwEbeamServe.log for errors.

 

gwEbeamServeWF:

  1. Change /etc/init.d/st.gwEbeamServeWF on lcls-daemon3 to use CMDPATH=/usr/local/lcls/tools/gateway/script/st.gwEbeamServeWF64
  2. Restart gateway:

    [laci@lcls-daemon3]$ /etc/init.d/st.gwEbeamServeWF restart
  3. Verify that only OTRS:DMP1:695:* PVs can be seen from Photon/PCDS subnet clients.
  4. Verify that the lclshome->Network (Global)->PV Gateway Diag->Ebeam Serve WF display is repopulated after the restart.
  5. Check /u1/lcls/tools/gateway/gwEbeamServeWF.log for errors.


lcls-daemon10

gwLCLS4FACET:

  1. Change /etc/init.d/st.gwLCLS4FACET on lcls-daemon10 to use CMDPATH=/usr/local/lcls/tools/gateway/script/st.gwLCLS4FACET64
  2. Restart gateway:

    [laci@lcls-daemon10]$ /etc/init.d/st.gwLCLS4FACET restart
  3. Verify that LCLSIOC subnet PVs can be seen from FACETCA subnet clients.
  4. Verify that the lclshome->Network (Global)->PV Gateway Diag->LCLS 4 FACET display is repopulated after the restart.
  5. Check /u1/lcls/tools/gateway/gwLCLS4FACET.log for errors.

 

gwLCLS4LCLSII:

  1. Change /etc/init.d/st.gwLCLS4LCLSII on lcls-daemon10 to use CMDPATH=/usr/local/lcls/tools/gateway/script/st.gwLCLS4LCLSII_64
  2. Restart gateway:

    [laci@lcls-daemon10]$ /etc/init.d/st.gwLCLS4LCLSII restart
  3. Verify that LCLSIOC subnet PVs can be seen from LCLS2IOC subnet clients.
  4. Check /u1/lcls/tools/gateway/gwLCLS4LCLSII.log for errors.


lcls-prod01

gwLCLSPUB:

  1. Change /etc/init.d/st.gwLCLSPUB on lcls-prod01 to use CMDPATH=/afs/slac/g/lcls/tools/gateway/script/st.gwLCLSPUB64
  2. Restart gateway:

    [laci@lcls-prod01]$ /etc/init.d/st.gwLCLSPUB restart
  3. Verify that LCLS production PVs can be seen when running lclshome on LCLSDEV/LCLSDMZ nodes (e.g., mcclogin).
  4. Verify that the lclshome->Network (Global)->PV Gateway Diag->LCLS PUB display is repopulated after the restart.
  5. Check /nfs/slac/g/lcls/tools/gateway/gwLCLSPUB.log for errors.

 

gwLCLSARCH0:

Archiver Gateways should be stopped and restarted one at a time to independently verify that ACLs are working properly.

  1. Change /etc/init.d/st.gwLCLSARCH0 on lcls-prod01 to use CMDPATH=/afs/slac/g/lcls/tools/gateway/script/st.gwLCLSARCH0_64
  2. Restart gateway:

    [laci@lcls-prod01]$ /etc/init.d/st.gwLCLSARCH0 restart
  3. Verify that the lclshome->Network (Global)->PV Gateway Diag->LCLS ARCH0 display is repopulated after the restart.

  4. Check /nfs/slac/g/lcls/tools/gateway/gwLCLSARCH0.log for errors.

 

gwLCLSARCH1:

Archiver Gateways should be stopped and restarted one at a time to independently verify that ACLs are working properly.

  1. Change /etc/init.d/st.gwLCLSARCH1 on lcls-prod01 to use CMDPATH=/afs/slac/g/lcls/tools/gateway/script/st.gwLCLSARCH1_64
  2. Restart gateway:

    [laci@lcls-prod01]$ /etc/init.d/st.gwLCLSARCH1 restart
  3. Verify that the lclshome->Network (Global)->PV Gateway Diag->LCLS ARCH1 display is repopulated after the restart.
  4. Check /nfs/slac/g/lcls/tools/gateway/gwLCLSARCH1.log for errors.

     

gwLCLSARCH2:

Archiver Gateways should be stopped and restarted one at a time to independently verify that ACLs are working properly.

  1. Change /etc/init.d/st.gwLCLSARCH2 on lcls-prod01 to use CMDPATH=/afs/slac/g/lcls/tools/gateway/script/st.gwLCLSARCH2_64
  2. Restart gateway:

    [laci@lcls-prod01]$ /etc/init.d/st.gwLCLSARCH2 restart
  3. Verify that the lclshome->Network (Global)->PV Gateway Diag->LCLS ARCH2 display is repopulated after the restart.

  4. Check /nfs/slac/g/lcls/tools/gateway/gwLCLSARCH2.log for errors.

 

gwLCLSARCH3:

Archiver Gateways should be stopped and restarted one at a time to independently verify that ACLs are working properly.

  1. Change /etc/init.d/st.gwLCLSARCH3 on lcls-daemon10 to use CMDPATH=/afs/slac/g/lcls/tools/gateway/script/st.gwLCLSARCH3_64
  2. Restart gateway:

    [laci@lcls-prod01]$ /etc/init.d/st.gwLCLSARCH3 restart
  3. Verify that the lclshome->Network (Global)->PV Gateway Diag->LCLS ARCH3 display is repopulated after the restart.

  4. Check /nfs/slac/g/lcls/tools/gateway/gwLCLSARCH3.log for errors.

     


lcls2-daemon10

gwLCLSII4LCLS:

  1. Change /etc/init.d/st.gwLCLSII4LCLS on lcls2-daemon10 to use CMDPATH=/usr/local/lcls/tools/gateway/script/st.gwLCLSII4LCLS64
  2. Restart gateway:

    [laci@lcls2-daemon10]$ /etc/init.d/st.gwLCLSII4LCLS restart
  3. Verify that LCLS2IOC subnet PVs are readable and writable from LCLSIOC subnet clients.

  4. Check /u1/lcls/tools/gateway/gwLCLSII4LCLS.log for errors.


FACET Gateway Test Procedures

facet-daemon1

gwFACET4LCLS:

  1. Change /etc/init.d/st.gwFACET4LCLS on facet-daemon1 to use CMDPATH=/usr/local/facet/tools/gateway/script/st.gwFACET4LCLS64
  2. Restart gateway:

    [flaci@facet-daemon1]$ /etc/init.d/st.gwFACET4LCLS restart
  3. Verify that FACETCA subnet PVs can be seen from LCLSIOC subnet clients.


lcls-prod01

gwFACETPUB:

  1. Change /etc/init.d/st.gwFACETPUB on lcls-prod01 to use CMDPATH=/afs/slac/g/lcls/tools/gateway/script/st.gwFACETPUB64
  2. Restart gateway:

    [laci@lcls-prod01]$ /etc/init.d/st.gwFACETPUB restart
  3. Verify that FACETCA subnet PVs can be seen when running facethome on LCLSDEV/LCLSDMZ nodes (e.g., mcclogin).

 

gwEXP2FACET:

  1. Change /etc/init.d/st.gwEXP2FACET on lcls-prod01 to use CMDPATH=/usr/local/lcls/tools/gateway/script/st.gwEXP2FACET64
  2. Restart gateway:

    [laci@lcls-prod01]$ /etc/init.d/st.gwEXP2FACET restart
  3. gwEXP2FACET not currently in use.

 

gwFACETARCH:

  1. Change /etc/init.d/st.gwFACETARCH on lcls-daemon10 to use CMDPATH=/usr/local/lcls/tools/gateway/script/st.gwFACETARCH64
  2. Restart gateway:

    [laci@lcls-prod01]$ /etc/init.d/st.gwFACETARCH restart
  3. Verify that the following PV patterns are archived in the FACET Archiver according to the permissions below:

    [laci@lcls-prod01]$ cat $TOOLS/gateway/config/gwFACETARCH.dat
    ...
    # support the gateway internal statistics
    # Serve all FACET PVs 
    .*  ALLOW




 

Test Facilities Gateway Test Procedures

testfac-daemon2

gwACCTESTPUB:

  1. Change /etc/init.d/st.gwACCTESTPUB on testfac-daemon2 to use CMDPATH=/afs/slac/g/acctest/tools/gateway/script/st.gwACCTESTPUB64
  2. Restart gateway:

    [acctf@testfac-daemon2]$ /etc/init.d/st.gwACCTESTPUB restart
  3. Verify that ACCTESTFAC subnet PVs can be seen when running xtahome on LCLSDEV/LCLSDMZ nodes (e.g., mcclogin).

 



Cryo Gateway Test Procedures

cryo-daemon1

gwCRYO4LCLS:

  1. Change /etc/init.d/st.gwCRYO4LCLS on cryo-daemon1 to use CMDPATH=/usr/local/lcls/tools/gateway/script/st.gwCRYO4LCLS64
  2. Restart gateway:

    [laci@cryo-daemon1]$ /etc/init.d/st.gwCRYO4LCLS restart
  3. Verify that CRYOSRV subnet PVs can be seen from LCLSIOC and LCLS2IOC subnet clients.

 