Reason for change

We request to put  AlarmsCfg-07-00-04 in production. In the new tag the warning  limit on the  Lac Threshold have been slightly relaxed for two CAL channels (tower 13 layer 1 column1 pos face and tower 13 layer 1 column 4 neg face). A detailed description is given  in the last section of this page.

Test Procedure

We have processed monitoring products from real on-orbit data (LPA) locally with this version of AlarmsCfg.

Rollback procedure

The package can be rolled back to the previous version by flipping a soft link. Also note that the package is completely independent from any other package running in the pipeline and will not cause a version change of L1Proc.

CCB JIRA

SSC-408 - Request to update alarm settings in L1Proc 5.4 (AlarmsCfg-07-00-04 ) 

Details (release notes for AlarmsCfg-07-00-04)

Relaxing the warning limit for the quantities Lac_Thresholds_FacePos_TH1_TowerCalLayerCalColumn (for tower 13, layer 1, column 1) and  Lac_Thresholds_FaceNeg_TH1_TowerCalLayerCalColumn (for tower 13, layer 1, column 4) in xml/recon_eor_alarms.xml . In both cases the upper warning limit has been changed from 2.75 to 2.8
 

Relevant thread(s):

https://www-glast.stanford.edu/protected/mail/datamon/15245.html 

  • No labels