PV Name

Purpose

EGU

Limits

 

KLYS_LLRF:IN20:RH:LOB_PDES

Desired Phase used by LOB local feedback

degrees; absolute

 

 

KLYS_LLRF:IN20:RH:LOB_P

Desired Phase for Beam-based feedback only

degrees; absolute

none provided- to be calculated by beam-based feedback

 

KLYS_LLRF:IN20:RH:L0B_PAVG

actual phase readback (avg of multiple channels): used by beam-based feedback, slc-aware readback arrys,

degrees; absolute

none provided

 

 

 

 

 

 

KLYS_LLRF:IN20:RH:L0B_ADES

Desired Amplitude (or Power?) used by LOB local feedback

volts; absolute

HOPR, LOPR

 

KLYS_LLRF:IN20:RH:L0B_A

Desired amplitude (or Power?) for beam-based feedback only

volts; absolute

HOPR, LOPR

 

KLYS_LLRF:IN20:RH:L0B_AAVG

actual amplitude readback (avg of multiple channels): used by beam-based feedback, slc-aware readback arrys,

volts; absolute

HOPR, LOPR

 

 

 

 

 

 

KLYS_LLRF:IN20:RH:G_L0_FB_CTL

When this in PV is ON, beam-based feedback locks out others users and other applications from setting L0B_A/P, or L0B_ADES/PDES, and the local feedback is turned off. Beam-based feedback is responsible for setting this PV ON when starting, setting it OFF when stopping.

 


 

 

 

 

 

 

...

  • These PV names and usages are a template for L1S and the BC1 energy beam-based feedback
  • TBD: the _A, _ADES, _AAVG may be power, not voltage - may need to use _V, _VDES, _VAVG - Dayle to confirm

RESOLVED:

  • The Beam-based feedback takes precidence over local feedback, other applications, and user inputs. when Beam-based feedback is on, local feedback and user other inputs are disabled
  • the L0B_A, L0B_P PVs will be an absolute value, not a delta.
  • Both amplitude and phase will be available as an actuator for the Beam-based feedback for DL1.  Only one of these will be used at a time

UNRESOLVED:

  • What to do with Local feedback when there are user inputs Beam-based feedback is OFF, and there are other applications or users trying to set amp / phase  (such as correlation plots, etc)?
  • TBD: the _A, _ADES, _AAVG may be power, not voltage - may need to use _V, _VDES, _VAVGAre all Klystrons and TCAVs to be made available