PV Name

Purpose

EGU

Limits

 

LLRF:IN20:RH:LOB_PDES

Desired Phase used by LOB local feedback, users, apps other than beam-based feedback  - may be used as readback by LEM

degrees; full range, not delta

 

 

LLRF:IN20:RH:LOB_P

Desired Phase for Beam-based feedback only

degrees; full range

none provided- to be calculated by beam-based feedback

 

LLRF:IN20:RH:L0B_PAVG

actual phase readback (avg of multiple channels): used by beam-based feedback, slc-aware readback arrys,

degrees; full range

none provided

 

 

 

 

 

 

LLRF:IN20:RH:L0B_ADES

Desired Amplitude used by LOB local feedback, users, apps other than beam-based feedback - may be used as readback by LEM

MeV;full range

HOPR, LOPR

 

LLRF:IN20:RH:L0B_A

Desired amplitude for beam-based feedback only

MeV;full range

HOPR, LOPR

 

LLRF:IN20:RH:L0B_AAVG

actual amplitude readback (avg of multiple channels): used by beam-based feedback, slc-aware readback arrys,

MeV;full range

HOPR, LOPR

 

 

 

 

 

 

LLRF:IN20:RH:G_L0_FB_CTL

When this PV is ON, beam-based feedback locks out users and other applications from setting L0B_A/P, or L0B_ADES/PDES.
Beam-based feedback is responsible for setting this PV ON when starting, setting it OFF when stopping.  When this PV is set OFF, the _ADES and _PDES PVs are set to supervisory mode and accept new values from users and applications other than beam-based feedback; _P and _A simply reflect the values of _ADES and _PDES.  Whe this PV is ON the _ADES and _PDES PVs are set to closed loop mode, and do not accept new values from users and applications. The _P and _A PVs accept values from beam-based feedback, and their values are reflected in _ADES, _PDES

 


 

 

 

 

 

 

NOTES

RESOLVED:

UNRESOLVED: