Table 1.3 is a subset of EPICS PV Attributes for a single device. For a complete list of attributes and a detailed description please read the Magnet Application Programming Interface.

Note: as of Sep 21, 2006 the Magnet Controls EPICS PV Attributes list is still under development. So check for updates.

EPICS PV Attributes

Table 1.3

EPICS PV Attribute

SLC Secondary

Description

BEFF | | Effective B-field value (for mains w/trim=main+trim B-field)

BDES | BDES | Desired B-field value

BCTRL | | Set B field value, then perturb, updates BDES

BACT | BACT | Physical Units val converted from IACT

BMON | BMON | Physical Units val converted from IMON

BMAX | BMAX | Maximum Operating B field

BMIN | | Minimum Operating B-field

BDES.DRVL | | Minimum Operating B-field

BCDES.DRVH | | Maximum Operating B-field

TRIMBTOL | TOLS(1) | Absolute Trim Tolerance (Warning Delta)

TRIMBTOLR | TOLS(2) | Relative Trim Tolerance (Warning Fraction)

CHCKTOL | TOLS(3) | Absolute Check Tolerance (Alarm Delta)

CHCKTOLR | TOLS(4) | Relative Check Tolerance (Alarm Fraction)

BDELTAS.F | TOLF | Monitor Fraction

CALBTOD | CTIM | Last successful calibration time

TRIMTOD | TTIM | Last successful stardardize time

STDZTOD | ZIMM | Last successful trim time

CTRL | - | Magnet control function, see table 1.5

HSTACTRL

-

Translates SLC HSTA to individual EPICS records

HSTA

HSTA

Hardware Status

CALBDISABLE | - | 1=disable, 0=enable

FBCKENABLE | - | 1=enabled, 0=disabled

OUTOFSERVICE

-

0=in service; 1=out-of-service

STDZDIRECTION | - | 0=Up, 1=Down

STDZENABLE | - | 1=enabled, 0=disabled

TRIMDISABLE | - | 1=disable, 0=enabled

UNAVAIL

-

1=unavailable; 0=available

ONOFFCTRL

-

1=on/off control; 0=no on/off control

NOANLGCTRL

-

1=no analog control ps; 0=analog control ps

OPTURNEDOFF

-

1=ps turned off by operator; 0=ps not turned off by operator

TRIPPED

-

1=ps tripped; 0=ps not tripped

...

POLYCOEF.A to L

IVBU/D

Polynomial Coefficients

STAT | STAT | Status

CALBOK | - | 1=Calibration successful

STDZOK | - | 1=Standardize successful

TRIMOKOK | - | 1=Trim successful

FBCKCTRL | - | 1=Magnet under feedback control

CTRLSTATE

MBBO

Status of Magnet Control Function

BUSY

BI

Busy State of Magnet Control Function

STDZIMIN | IMMS(1) | Min current during standardization

STDZIMAX | IMMS(2) | Max current during standardization

STDZIFINAL | IMMS(0) | Final current set point

STDZRAMPRATE | - | Standardize di/dt

STDZTOD.TIME | KTIM | Last successful standardization time

STDZLOSTTOD | ZTIM | Last time standardization lost

TRIMTOD | TTIM | Last trim time

TRIMTRYCNT | ITRY | # of attempts required for trim

Machine Areas with Magnets

Table 1.4

Production

Area

EPICS IOC

SLC Aware Micro

SLC Micro

SLC DGRP

Injector

IOC-IN20-MG01

IM20

     

    Linac Sector 21

    IOC-LI21-MG01

    LM21

    LI21

     

    Linac Sector 22

    IOC-LI22-MG01

    LM22

    LI22

     

    Linac Sector 23

    IOC-LI23-MG01

    LM23

    LI23

     

    Linac Sector 24

    IOC-LI24-MG01

    LM24

    LI24

     

    Linac Sector 25

    SIOC-LI25-MG01

      LI25

       

      Linac Sector 26

      SIOC-LI26-MG01

        LI26

        Linac Sector 27

        SIOC-LI27-MG01

          LI27

           

          Linac Sector 28

          SIOC-LI28-MG01

            LI28

             

            Linac Sector 29

            SIOC-LI29-MG01

              LI29

               

              Linac Sector 30

              SIOC-LI30MG01

                LI30

                 

                Beam Switch Yard (B136)

                IOC-BSY0-MG01

                  CA11

                   

                  Linac-To-Undultor (B005)

                  IOC-LTU0-MG01

                     

                     

                    Linac-To-Undulator(B911)

                    IOC-LTU1-MG01

                       

                       

                      Linac-To-Undulator(B912)

                      IOC-LTU1-MG02

                         

                         

                        Undulator (B913)

                        IOC-UND1-MG01

                           

                           

                          E-DUMP &Undulator (B921)

                          IOC-DMP1-MG01

                             

                             

                            Development

                            Test 1

                            XL01

                            XX01

                             

                             

                            Test 2

                            IOC-B15-MG01

                            XX02

                             

                             

                            Test 3

                            LCLSDEV-17

                            XX03

                             

                             

                            ...