- Signal state change to 33 (Burst close signal received)
- Move (MA) to positive closed position (P1)
- If error checking is enabled (Ec=1), check drift at previous, assumed positive negative closed position (call X8X9) (this is redundant here)
- Hold until movement complete
- Set Df=1 to indicate slits are at positive closed position
- Copy current encoder count (C2) to shadow register Cs
- Signal state change to 91 (Move to positive closed position complete)
- Return
...
- Signal state change to 40 (Fast Open Init)
- Load fast open speeds
- Calculate target position using drift of current position (X9)
- Move (MA) to the open position (P0)
- If error checking is enabled (Ec=1), check drift at previous, assumed positive closed position (call X8)
- Hold until movement complete
- Set Df=0 to indicate that slits are in open position
- Signal state change to 41 (Fast open complete)
- Goto mode select
...
- Signal state change to 50 (Fast close init)
- Load fast close speedsCalculate target position using drift of current position (X9)
- If neither at position P1 (positive closed) nor at position P2 (negative closed), then
- Move (MA) to the positive closed position (P1)
- If error checking is enabled (Ec=1), check drift at previous, assumed negative closed position (call X8)
- Hold until movement complete
- Set Df=1 to indicate that slits are in positive closed position
- Copy current encoder count to Cs for future drift checks
- EndIf
- Signal state change to 51 (Fast close complete)
- Goto mode select
...