Panel |
---|
Devices are named with a sequence of characters in the following format: Wiki Markup |
---|
{center}{*}DeviceType* : *Area* : *Position{*}{center} |
An example of a device name looks like this: Wiki Markup |
---|
{center}{*}QUAD* : *IN20* : *122* {center} |
There are functions and parameters associated with devices, which also need to be identified. An Attribute field provides that information: Wiki Markup |
---|
{center}{*}DeviceType* : *Area* : *Position* : *Attribute* {center} |
Wiki Markup |
---|
The _DeviceType_ and _Position_ fields also have optional characters. We can denote optional symbols with *\[* and *\]*, so the names can be described as: |
Wiki Markup |
---|
{center}*\[* DeviceType *\]* *DeviceDetail* : *Area *: *\[* PositionPrefix *\]* *Position* : *Attribute* {center} |
To summarize: - A Device is named by 3 fields, separated by 2 colons.
- A function or parameter of a device, known internally to the Control System as a Process Variable (PV) is named by the 3-field device name followed by another colon, and the Attribute field.
|
...
Table 1.0 |
---|
Value | Device Type | SLC-Aware | Controllable |
---|
BEND | Bend (Large Dipole) Magnet | Y | Y |
BTRM | Bend Magnet Trim Windings | Y | Y |
KICK | Kicker Magnet | N | Y |
MGNT | General Magnet | N | N |
QTRM | Quad Magnet Trim Windings | Y | Y |
QUAD | Quadrupole Magnet | Y | Y |
SOLN | Solenoid Magnet | Y | Y |
XCOR | Horizontal Steering Corrector Magnet | Y | Y |
YCOR | Vertical Steering Corrector Magnet | Y | Y |
The following is a list of power supplies
Table 1.0.1 |
---|
Value | Device Type | SLC-Aware | Controllable |
---|
HVPS | High Voltage Power Supply | Y | Y |
LGPS | Large Power Supply | Y | Y |
SMPS | Small Power Supply | N | Y |
The following table lists RF system Compound DeviceTypes:
Table 1.1 |
---|
Value | Device Type | SLC-Aware | Controllable |
---|
ACCL | Accelerating Section | N | Y |
KLYS | Klystron | N | Y |
LLRF | Low Level RF | N | Y |
PCAV | Beam Phasing Cavity | N | Y |
TCAV | Transverse Deflecting Cavity | N | Y |
REFS
| Machine Parameters Set Points
| N
| | Y | |
The following table lists vacuum Compound DeviceTypes:
Table 1.2 |
---|
Value | Device Type | SLC-Aware | Controllable |
---|
VGBA | Vacuum Gauge Baratron | N | N |
VGKL | Vacuum Gauge associated with a Klystron | N | N |
VGPR | Vacuum Pirani Gauge | N | N |
VGCC | Vacuum Cold Cathode Gauge | N | Y |
VGTC | Vacuum ThermoCouple Gauge | N | N |
VGCP | Vacuum Convection-enhanced Pirani Gauge | N | N |
VGHF | Vacuum Hot Filament Gauge | N | Y |
VGOS | Vacuum Overpressure Switch | N | N |
VGXX | Combination Vacuum Gauge | N | N |
VVKL | Vacuum Valve associated with a Klystron | N | Y |
VVPG | Vacuum Pneumatic Gate Valve | N | Y |
VVMG | Vacuum Manual Gate Valve | N | N |
VVPR | Vacuum Pneumatic Roughing Valve | N | Y |
VVMR | Vacuum Manual Roughing Valve | N | N |
VVPF | Vacuum Pneumatic Fore Valve | N | Y |
VVMF | Vacuum Manual Fore Valve | N | N |
VVPV | Vacuum Pneumatic Vent Valve | N | Y |
VVMV | Vacuum Manual Vent Valve | N | N |
VVFS | Vacuum Fast (Shutter) Valve | N | Y |
VVFL | Vacuum (Mass) Flow Valve | N | Y |
VPKL | Vacuum Pump associated with a Klystron | N | Y |
VPDF | Diffusion Pump | N | N |
VPCR | CRyo Pump | N | Y |
VPIO | IOn Pump | N | Y |
VPTM | TurboMolecular Pump | N | Y |
VPTS | Ti Sublimation Pump | N | Y |
VPFO | Fore Pump | N | Y |
VPRO | Roughing Pump | N | Y |
The following table lists system Compound DeviceTypes:
Table 1.3 |
---|
Value | Device Type | SLC-Aware | Controllable |
---|
AIR | Compressed Air System for Pneumatic Control | N | N |
NITR | Process Nitrogen Gas for Attenuator/Detector | N | Y |
ARGO | Process Argon Gas for Attenuator/Detector | N | Y |
BCS | Beam Containment System | N | N |
HVAC | Heating, Ventilation, and AC System | N | N |
LASR | Laser System | N | N |
WATR | Water System | N | N |
MPS | MPS (Machine Protection System) | N | N |
PPS | PPS (Personel Protection System) | N | N |
...
Table 1.4 |
---|
Value | Device Type | SLC-Aware | Controllable |
---|
ARRY | Group of BSA Channels for SLC-Aware only | Y | N |
APD | Avalanche Photo Diode | N | N |
BLEN | Bunch Length Monitor | Y | N |
BPMS | Beam Position Monitor | Y | N |
CAMR | Camera for Optics and Beam Profile | N | Y |
CRAD | Cerenkov Radiator | N | N |
FARC | Faraday Cup | N | N |
JMTR | Joule Meter (for Laser) | N | N |
MDEF | SLC Measurement Definition | Y | Y |
EDEF | EPICS Event Measurement Definition | N | Y |
OTRS | OTR screen | N | Y |
PD | Photo Diode | N | N |
PHOS | Phosphor screen | N | Y |
PMT | Photo Multiplier Tube | N | N |
TORO | Toroid | Y | N |
YAGS | YAG screen | N | Y |
PATT | Timing Pattern | N | N |
WPM | Wire Position Monitor | N | N |
...
Table 1.5 |
---|
Value | Device Type | SLC-Aware | Controllable |
---|
BMLN | Beam Line | N | N |
CAMW | Web Cam | N | N |
CATH | Cathode | N | N |
COLL | Collimator | N | Y |
DIAG | Diagnostic | N | Y |
DUMP | Beam Dump | N | N |
EXPT | Experiment | N | Y |
FAN | Fan | N | Y |
FOIL | Diagnostic Foils, Slotted Foil | N | N |
GATT | Gas Attenuator | N | Y |
GDET | Gas Detector | N | Y |
GUN | Gun | N | Y |
HLS | Hydrostatic Leveling Sensor | N | N |
KMON | K-monochromator | N | Y |
LHTR | Laser Heater | N | N |
LION | Long ION chamber | N | N |
LVDT | Linear Variable Differential Transformer | N | N |
MASK | Mask | N | N |
MIRR | Optical Mirror | N | Y |
PICS | Protection Ion Chamber Signal | N | N |
PICM | MPS Protection Ion Chamber Signal | N | N |
PLIC | Panofsky Long Ion Chamber | N | N |
PKLS | Pockels Cell (photon attenuation) | N | Y |
ROOM | Room, vault, or tunnel | N | N |
RTD | Resistive temperature detector | N | N |
SATT | Solid Attenuator | N | Y |
SBST | Sub-Booster | N | Y |
SHUT | Shutter (mechanical, optical shutter) | N | Y |
SLIT | Slit (mechanical, 2- or 4-jaw) | N | Y |
STPR | Beam Stopper | N | Y |
SPLR | Beam Spoiler | N | Y |
TRGT | Target | N | Y |
TANK | Diagnostic Tank | N | Y |
THZR | THz Radiator | N | Y |
TIU | Tone Interrupt Unit (for MPS) | N | N |
WIRE | Wire Scanner | N | Y |
WKFL | Wakefield Shield | N | Y |
XTAL | Crystal Monochromator | N | Y |
BKHF | Beckhoff coupler | N | Y |
SCTR | Beam Scatterer | N | Y |
The following table lists what are currently considered Component DeviceTypes that are either controllers or control modules:
Table 1.6 |
---|
Value | Device Type | Controllable |
---|
PSC | PS Controller | Y |
IOC | Input/Output Controller | Y |
MOC | Motor Controller | Y |
PAC | Phase and Amplitude Controller | Y |
PLC | Programmable Logic Controller | Y |
VGC | Vacuum Gauge Controller | Y |
VPC | Vacuum Pump Controller | Y |
VVC | Vacuum Valve Controller | Y |
VFC | Vacuum Flow Controller | Y |
The following table lists Component DeviceTypes for control system modules and instruments:
Table 1.7 |
---|
Value | Device Type | SLC-Aware | Controllable |
---|
ADC | Analog-to-Digital Conversion Module | N | N |
AFG | Arbitrary Function Generator | N | Y |
DAC | Digital-to-Analog Conversion Module | N | Y |
BPMP | Beam Position Module | Y | N |
DTIZ | Digitizer | N | N |
CHAS | Input/Output chassis | N | N |
CRAT | Input/Output (VME) Crate | Y | Y |
DI | Digital Input Module | N | N |
DIAG | Diagnostics | N | N |
DIO | Digital Input/Output Module | N | N |
DO | Digital Output Module | N | N |
DMM | Digital MultiMeter | N | Y |
DVM | Digital Voltmeter | N | Y |
EVG | Event Generator for Timing | N | Y |
EVR | Event Receiver for Timing | Y | Y |
MCOR | MCOR for Magnet PS | N | Y |
MODU | Non-specific Module | N | Y |
MPG | Master Pattern Generator | N | Y |
PAD | Phase and Amplitude Detector | N | N |
PDU | Pulsed Delay Unit | N | Y |
PMTR | Power Meter | N | Y |
PMGR | Power Management Module | N | Y |
PNET | Pnet Module | N | N |
PSC | Ethernet Power Supply Controller | N | Y |
SCLR | Scaler Module | N | N |
SCOP | Oscilloscope | N | Y |
TRIG | Spare Timing Trigger | N | Y |
The following table lists Component DeviceTypes for the network:
Table 1.8 |
---|
Value | Device Type | Controllable |
---|
ACSW | AC Switch | Y |
GPIB | GPIB/LAN Gateway | Y |
RTR | Router | N |
SWH | Ethernet Switch | N |
TS | Terminal Server | Y |
UPS | Uninterruptible Power Supply | N |
WKUP | Walk-up ethernet connection | N |
IOC | EPICS IOC | Y |
PLC | Programmable Logic Controller | Y |
PSC | Power Supply Controller | Y |
CAMR | Camera for Beam Line Optics | Y |
CRAT | Intelligent VME Crates | Y |
PC | Computer that is not an IOC | Y |
...
Table 1.13 |
---|
Attribute | Function Affected or Parameter Described | Controllable |
---|
VOLT or V or VACT | Actual Voltage | N |
VOLTSETPT or VSETPT | Voltage Setpoint | Y |
VOLTRBCK or VRBCK | Voltage Setpoint Readback | N |
VDES | Desired Voltage | Y |
I or IACT | Current Readback | N |
ISETPT | Current Setpoint | Y |
IDES | Desired Current | Y |
B or BACT | Magnetic Field Readback | N |
BDES | Desired Magnetic Field | Y |
AMPL or AACT | Amplitude Readback | N |
AMPLSETPT | Amplitude Setpoint | Y |
ADES | Desired Amplitude | Y |
PHASE or PACT | Phase Readbask | N |
PHASESETPT | Phase Setpoint | Y |
PDES | Desired Phase | Y |
MAD | Mad Name | N |
Z | Z-Position | N |
PRESS or P | Pressure, such as Vacuum | N |
PRESSSETPT or PSETPT | Pressure, such as Vacuum | N |
TEMP | Temperature | N |
TEMPSETPT | Temperature | N |
TMIT or Q | Bunch Charge | N |
FLOW | Flow Rate | N |
FLOWSETPT | Flow Rate | N |
SPEED | Speed | N |
RAMPRATE | Ramp Rate | N |
LOSSRATE | Loss Rate | N |
WIDTH | Pulse Width | N |
WIDTHSETPT | Pulse Width | Y |
DELAY | Pulse Delay | N |
DELAYSETPT | Pulse Delay | Y |
TDES | Pulse Delay | Y |
TABS | Absolute Time | N |
TIME | Delta Time | N |
TIMESETPT | Delta Time | Y |
TOD | Time-of-Day | N |
COUNT or CNT | Count | N |
COUNTSETPT or CNTSETPT | Count | Y |
CENTER or CTR | Center | N |
CENTERSETPT or CTRSETPT | Center | Y |
ID or IDENT | Unique (Integer) Identifier | N |
IDENTSETPT | Unique (Integer) Identifier | Y |
NAME | Unique (String) Identifier | N |
ENERGY | Energy | N |
ENERGYSETPT | Energy | Y |
POWER | Power | N |
POWERSETPT | Power | Y |
FREQ | Frequency | N |
FREQSETPT | Frequency | Y |
ANGLE | Angle | N |
ANGLESETPT | Angle | Y |
POSN | Position | N |
POSNSETPT | Position | Y |
GAP | Gap | N |
GAPSETPT | Gap | Y |
XAVG | Horizontal Value | N |
YAVG | Vertical Value | N |
ZAVG | Longitudinal Value | N |
UAVG | Diagonal Value | N |
SAVG | Beamline Position Value | N |
XRMS | Horizontal Value | N |
YRMS | Vertical Value | N |
ZRMS | Longitudinal Value | N |
URMS | Diagonal Value | N |
SRMS | Beamline Position Value | N |
XHIGH | Horizontal Value | N |
YHIGH | Vertical Value | N |
ZHIGH | Longitudinal Value | N |
UHIGH | Diagonal Value | N |
SHIGH | Beamline Position Value | N |
XLOW | Horizontal Value | N |
YLOW | Vertical Value | N |
ZLOW | Longitudinal Value | N |
ULOW | Diagonal Value | N |
SLOW | Beamline Position Value | N |
XSETPT | Horizontal Value | Y |
YSETPT | Vertical Value | Y |
ZSETPT | Longitudinal Value | Y |
USETPT | Diagonal Value | Y |
SSETPT | Beamline Position Value | Y |
XHIST | Horizontal Value | N |
YHIST | Vertical Value | N |
ZHIST | Longitudinal Value | N |
UHIST | Diagonal Value | N |
SHIST | Beamline Position Value | N |
CHECK | Check | Y |
CTRL | Do a Specific Action | Y |
GO | Do an Action | Y |
RESET | Reset | Y |
RESTART | Restart (stop and go) | Y |
STOP | Stop doing an Action | Y |
Examples
Here are a few examples of device names.
...