Page History
...
To view status of the 4 sequence engines (4 eventcodes per engine) execute "xpmpva DAQ:NEH:XPM:3" and select the "Groups/Eventcodes" tab. The "Master" column is important: it says which XPM controls which event code (in units of an "engine": 4 event codes). The "Ena" and "Dis" buttons (for the appropriate XPM!) can be used to change which XPM controls a particular engine.
Kristjan's tables of andor rates/readout times:
View file | ||||
---|---|---|---|---|
|
Practice Session April 3, 2024
Commands for 66Hz Andor running with 8kHz beam:
Code Block |
---|
8kHz beam + one camera (66Hz): rixgenerator --bunch_period 112 --periods 0.015385 --readout_time 0.005
8kHz beam + two cameras(1Hz + 66Hz): rixgenerator --bunch_period 112 --periods 1 0.015385 |