## Load record instances for Timing. 2 BSA PVs, a PMC EVR with rear Trigger Transition Board (TTB)
dbLoadRecords("db/EvrPmc.db","EVR=EVR:B34:EV05,CRD=0, SYS=SYS0")
dbLoadRecords("db/Pattern.db","IOC=IOC:B34:EV05, SYS=SYS0")
dbLoadRecords("db/Bsa.db","DEVICE=TRIG:B34:EV05, ATRB=COUNTER, SYS=SYS0")
dbLoadRecords("db/Bsa.db","DEVICE=TRIG:B34:EV05, ATRB=SINE, SYS=SYS0")
dbLoadRecords("db/PMC-trig.db", "LOCA=B34,UNIT=EV05,SYS=SYS0,IOC=IOC:B34:EV05")
dbLoadRecords("db/VME-TTB-trig.db", "LOCA=B34,UNIT=EV05,SYS=SYS0,IOC=IOC:B34:EV05")
give the first trigger, DEV0, a non-default name:
dbLoadRecords("db/VME-trig.db", "LOCA=UND1,UNIT=RM01,SYS=SYS0,IOC=IOC:UND1:RM01,DEV0=QADC:UND1:100:")
or in a substitutions file:
file Bsa.db
{
pattern {DEVICE, ATRB, SYS }
{ BLM:UND1:1345, QDCRAW, SYS0 }
{ BLM:UND1:1435, QDCRAW, SYS0 }
EvrPmc
#==============================================================================
# Abs: LCLS EVR records for bpm EVRs
#
# Name: EVR.substitutions
#
# Macros:
#
# evr.db - instantiates an EVR record.
# Associated display is evrDiags.edl.
# DEV Name of EVR - EVR:<loca>:<unit>
# CARD EVR card number starting at 0 (matches card number in ErConfigure).
#
# evrEventCtrl.db - instantiates a record for an EVR event.
# Associated display is evrTriggerDiags.edl.
# DEV Name of EVR - EVR:<loca>:<unit>
# CARD EVR card number starting at 0 (matches card number in ErConfigure).
#
# Optional:
# SYS SYS code for the system where this EVR is deployed:
# SYS0 for LCLS
# SYS1 for FACET
# SYS2 for LCLS II
# IDn Defining SYS will select the most commonly used event code numbers for the
# specific system. To override these defaults, define IDn where n is 1-14.
# Event code number. To find all available event codes:
# lclshome -> Event -> Events... (in the EVG IOC bo14).
# This display brings up all the event that are beam-dependent.
# For events that are beam-independent (constant or standby), select
# "Time Slot 1 to 6 Event Codes". Find the event that you want to trigger one or
# more devices connected to the EVR. Use number in the Event Code column.
# Also check sharepoint spreadsheet:
# Controls -> Timing -> timingEventCodes
# NOTE: There is a dependency on event code assignments and triggers.
# When changing event code assignments below, also change the appropriate
# <ioc>trig.substitutions file!
# NOTE: If you don't need to use all 14 event codes, populate the spare records
# with other event codes from the "Time Slot 1 to 6 Event Codes" display.
#
...