PurposeBase PVConnectionCabled?Operational?
Permissive Signal
Trigger MEC:USR:AIN:9

User timing and firing unit permissive output (+5V 100 microsec pulse) to R62 EK9000, second  KL3404 (card 11), first channel, PV MEC:USR:AIN:9.

KL3404 specs are "4-channel analog input, voltage, ±10 V, 12 bit, single-ended"

May need pulse extended with, e.g. with a function generator, for detection by PLC.

Yes

...