DescriptionPV name
Signal valuesRegister
PV typeSignal valuesPLC's I/O typeModbus AddressPLC register name
Reset Interlocks/LatchesPV nameinputSignal valuesREQ7a0.i0
Pause HeartbeatPV nameinputSignal valuesREQ6a0.i1
HW EnablePPS:AAA:N:HwEnableoutputDisabled (MAJOR), Enabled (NO_ALARM)RT-IN7a0.o0
LCLS SecurePPS:AAA:N:LclsSecureoutputNot_Secure (MAJOR), Secure (NO_ALARM)RT-IN6a0.o1
RSY SecurePPS:AAA:N:RsySecureoutputNot_Secure (MAJOR), Secure (NO_ALARM)RT-IN5a0.o2
BSY BSOICs OK (AKA BSOIC Group-C)BSOC:BSY0:1:SumyoutputFault (MAJOR), Ok (NO_ALARM)RT-IN4a0.o3
PLC2 panel Stopper-Enable KeyswitchPPS:AAA:N:StopperEnableoutputNot_Enabled (MAJOR), Enabled (NO_ALARM)RT-IN3a0.o4
Heartbeat IN (from opposite chain)PLC:AAA:N:HbXInoutputZero (NO_ALARM), One (NO_ALARM)RT-IN2a0.o5
Cross-Interlock input HX Permit (test-switched A or B)PLC:AAA:N:XInterlockInoutputNotReady (MAJOR), Ready (NO_ALARM)RT-IN1a0.o6
Cross-Interlock input SX Permit (test-switched A or B)PLC:AAA:N:XInterlockInoutputNotReady (MAJOR), Ready (NO_ALARM)RT-IN0a0.o7
Safety Relay Feedback – HX Summary OFFPPS:AAA:N:Sr[In|Out]outputFault (MAJOR), Ok (NO_ALARM)RT-IN15a0.o8
Safety Relay Feedback – SX Summary OFFPPS:AAA:N:Sr[In|Out]outputFault (MAJOR), Ok (NO_ALARM)RT-IN14a0.o9
Test Mode Keyswitch statusPLC:AAA:N:TestModeoutputTest (MAJOR), Normal (NO_ALARM)RT-IN13a0.o10
STP-D2 Summary OUTSTPR:AAA:N:StxxOutoutputTest (MAJOR), Normal (NO_ALARM)RT-IN8a0.o15
HX-Kicker Magnet OFFKICK:AAA:N:xxx:OffoutputNotOff (MAJOR), Off (NO_ALARM)RT-IN23a0.o16
HX-SepMrg Magnet OFFPV nameoutputSignal valuesRT-IN22a0.o17
BYKIK OFFKICK:AAA:N:xxx:OffoutputNotOff (MAJOR), Off (NO_ALARM)RT-IN21a0.o18
H1.3 ST1L0 INPV nameoutputSignal valuesRT-IN20a0.o19

HX-Kicker Admin enable: Input deriving as a summary from multiple administrative keyswitches (from ACR and NEH) , for allowing beam into the BSY. Operates similar to the “beam enable keyswitch”, but control is solely via PLC software, instead of interrupting physical circuit.

PPS:AAA:N:AcrEnableoutputNotEnabled (MAJOR), Enabled (NO_ALARM)RT-IN19a0.o20
Spare (HX-Kicker interlock)PPS:AAA:N:Spare$(bit)outputFault (MAJOR), Ok (NO_ALARM)RT-IN18a0.o21
STP-34 Summary OUTSTPR:AAA:N:StxxOutoutputTest (MAJOR), Normal (NO_ALARM)RT-IN95a0.o64
SX-Kicker Magnet OFFKICK:AAA:N:xxx:OffoutputNotOff (MAJOR), Off (NO_ALARM)RT-IN94a0.o65
SX-Septum Magnet OFFPV nameoutputSignal valuesRT-IN93a0.o66
BYKIKS Magnet OFFKICK:AAA:N:xxx:OffoutputNotOff (MAJOR), Off (NO_ALARM)RT-IN92a0.o67
CL-Merge Magnet OFFPV nameoutputSignal valuesRT-IN91a0.o68
SX-Kicker Admin enable: Input deriving as a summary from multiple administrative keyswitches (from ACR and NEH) , for allowing beam into the BSY. Operates similar to the “beam enable keyswitch”, but control is solely via PLC software, instead of interrupting physical circuit.PPS:AAA:N:AcrEnableoutputNotEnabled (MAJOR), Enabled (NO_ALARM)RT-IN90a0.o69
Spare (SX-Kicker interlock)PPS:AAA:N:Spare$(bit)outputFault (MAJOR), Ok (NO_ALARM)RT-IN89a0.o70
HX-Kicker and HX-SepMrg PermitPV nameoutputSignal valuesRT-OUT103a0.o72
HX-Kicker and HX-SepMrg Permit (RET)PV nameoutputSignal valuesRT-OUT102a0.o73
HX-Kicker/SepMrg Summary OFF to relayKICK:AAA:N:xxx:OffoutputNotOff (MAJOR), Off (NO_ALARM)RT-OUT101a0.o74
HX "Kicker Conditions OK" to PLC1PV nameoutputSignal valuesRT-OUT100a0.o75
SX-Kicker and SX-Septum PermitPV nameoutputSignal valuesRT-OUT99a0.o76
SX-Kicker and SX-Septum Permit (RET)PV nameoutputSignal valuesRT-OUT98a0.o77
SX-Kicker/Septum Summary Magnet OFF to relayKICK:AAA:N:xxx:OffoutputNotOff (MAJOR), Off (NO_ALARM)RT-OUT97a0.o78
SX "Kicker Conditions OK" to PLC1PV nameoutputSignal valuesRT-OUT96a0.o79
Cross-Interlock HX Permit (RT to testswitch for test mode)PLC:AAA:N:XInterlockTestoutputNotReady (MAJOR), Ready (NO_ALARM)RT-OUT111a0.o80
Cross-Interlock HX Permit (RT to testswitch for other chain)PLC:AAA:N:XInterlockOutoutputNotReady (MAJOR), Ready (NO_ALARM)RT-OUT110a0.o81
Cross-Interlock SX Permit (RT to testswitch for test mode)PLC:AAA:N:XInterlockTestoutputNotReady (MAJOR), Ready (NO_ALARM)RT-OUT109a0.o82
Cross-Interlock SX Permit (RT to testswitch for other chain)PLC:AAA:N:XInterlockOutoutputNotReady (MAJOR), Ready (NO_ALARM)RT-OUT108a0.o83
ACR Hardware alarmPPS:AAA:N:HwAlrmWarnoutputFault (MAJOR), Ok (NO_ALARM)RT-OUT107a0.o84
Heartbeat OUT (to opposite chain)PLC:AAA:N:HbXOutoutputZero (NO_ALARM), One (NO_ALARM)RT-OUT106a0.o85
LCLS SecurePPS:AAA:N:LclsSecureoutputNot_Secure (MAJOR), Secure (NO_ALARM)LAT104a0.o87
RSY SecurePPS:AAA:N:RsySecureoutputNot_Secure (MAJOR), Secure (NO_ALARM)LAT119a0.o88
BSY BSOICs OK (AKA BSOIC Group-C)BSOC:BSY:N:LclsSecureoutputFault (MAJOR), Ok (NO_ALARM)LAT118a0.o89
PLC2 panel Stopper-Enable KeyswitchPPS:AAA:N:StopperEnableoutputNot_Enabled (MAJOR), Enabled (NO_ALARM)LAT117a0.o90
STP-D2 Summary OUTSTPR:AAA:N:StxxOutoutputTest (MAJOR), Normal (NO_ALARM)LAT116a0.o91
HX-Kicker Magnet OFFKICK:AAA:N:xxx:OffoutputNotOff (MAJOR), Off (NO_ALARM)LAT115a0.o92
HX-SepMrg Magnet OFFPV nameoutputSignal valuesLAT114a0.o93
BYKIK OFFKICK:AAA:N:xxx:OffoutputNotOff (MAJOR), Off (NO_ALARM)LAT113a0.o94
H1.3 ST1L0 INPV nameoutputSignal valuesLAT112a0.o95
HX-Kicker Admin EnablePPS:AAA:N:AcrEnableoutputNotEnabled (MAJOR), Enabled (NO_ALARM)LAT127a0.o96
Spare (HX-Kicker interlock)PPS:AAA:N:Spare$(bit)outputFault (MAJOR), Ok (NO_ALARM)LAT126a0.o97
STP-34 Summary OUTSTPR:AAA:N:StxxOutoutputTest (MAJOR), Normal (NO_ALARM)LAT125a0.o98
SX-Kicker Magnet OFFKICK:AAA:N:xxx:OffoutputNotOff (MAJOR), Off (NO_ALARM)LAT124a0.o99
SX-Septum Magnet OFFPV nameoutputSignal valuesLAT123a0.o100
BYKIKS Magnet OFFKICK:AAA:N:xxx:OffoutputNotOff (MAJOR), Off (NO_ALARM)LAT122a0.o101
CL-Merge Magnet OFFPV nameoutputSignal valuesLAT121a0.o102
SX-Kicker Admin EnablePPS:AAA:N:AcrEnableoutputNotEnabled (MAJOR), Enabled (NO_ALARM)LAT120a0.o103
Spare (SX-Kicker interlock)PPS:AAA:N:Spare$(bit)outputFault (MAJOR), Ok (NO_ALARM)LAT135a0.o104
BCS Fault from PLC2PPS:AAA:N:BCSFaultoutputFault (MAJOR), Ok (NO_ALARM)RT-OUT132a0.o107
Heartbeat OKPLC:AAA:N:HrtBtOkoutputFault (MAJOR), Ok (NO_ALARM)RT-OUT132a0.o108
Magnet Status HX-Kicker/SepMrg FaultPV nameoutputSignal valuesRT-OUT131a0.o109
Magnet Status SX-Kicker/Septum FaultPV nameoutputSignal valuesRT-OUT130a0.o110
Magnet Status BYKIK FaultPV nameoutputSignal valuesRT-OUT129a0.o111
Magnet Status BYKIKS FaultPV nameoutputSignal valuesRT-OUT143a0.o112
Safety Relay HX Summary OFF OKPPS:AAA:N:Sr[In|Out]outputFault (MAJOR), Ok (NO_ALARM)RT-OUT142a0.o113
Safety Relay SX Summary OFF OKPPS:AAA:N:Sr[In|Out]outputFault (MAJOR), Ok (NO_ALARM)RT-OUT141a0.o114
Heartbeat OKPLC:AAA:N:HrtBtOkoutputFault (MAJOR), Ok (NO_ALARM)LAT137a0.o118
Magnet Status HX-Kicker/SepMrg FaultPV nameoutputSignal valuesLAT136a0.o119
Magnet Status SX-Kicker/Septum FaultPV nameoutputSignal valuesLAT151a0.o120
Magnet Status BYKIK FaultPV nameoutputSignal valuesLAT150a0.o121
Magnet Status BYKIKS FaultPV nameoutputSignal valuesLAT149a0.o122
Safety Relay HX Summary OFF OKPPS:AAA:N:Sr[In|Out]outputFault (MAJOR), Ok (NO_ALARM)LAT148a0.o123
Safety Relay SX Summary OFF OKPPS:AAA:N:Sr[In|Out]outputFault (MAJOR), Ok (NO_ALARM)LAT147a0.o124