- Mounting and Connecting to Power
- The C-more touch panel order with come with the touch screen, mounting clips, and a terminal block.
- Use the mounting clips (pictured below) to secure the panel, from the inside, to the door of the LSS box.
- Secure terminal block to back of panel.
- Connect one black wire (GND) from the ground terminal to grounded contact on rack.
- Ground terminal is second from the bottom and will be labelled with the ground symbol.
- Connect one blue wire (power) from the negative terminal to 24V contact on rack.
- Negative terminal is third from the bottom and will be labelled with a minus sign.
- Connecting to the PLC
- Connect HDMI cable from 15-pin port on back of panel to Data Communications Module port.
- Data Communications Module with HDMI cable connected:
- Connect HDMI cable from 15-pin port on back of panel to Data Communications Module port.
...