- Gun Temperature - 24 sensors.
- Gun Beam line - 12 14 sensors.
Laser Room Temperature Monitoring- 5 4 sensors located around the laser room for monitoring the ambient temperature. 5 4 sensors per optics table and 1 sensor per oscillator for monitoring respective temperatures. Additionally, there will be 1 be 4 sensor located near the UV table and 2 for the laser heater table on either side.
Phase Reference Line Temperature Monitoring - 4 sensors
Waveguide & Penetration Temperature Monitoring- 2 temperature 6 sensors / penetration. ( 6 sensors)in buncher penetration.
Facilities Temperature - Water - 4 sensors, Air - 2 sensors.
*** Immersion RTD`s
** PV Names are under review
...
No. | DESCRIPTION | PV Names |
---|
T0 | Supply/Inlet Temperature | GUN:GUNB:100:INLTTEMP*** |
T1 | Anode End Cap return temperature | GUN:GUNB:100:ANENDCAPRETTEMP*** |
T3 | Cathode End Cap return temperature | GUN:GUNB:100:CATHENDCAPRETTEMP*** |
T4 | Nose Return Temperature | GUN:GUNB:100:NOSERETTEMP*** |
T5 | Cavity Wall Return Temperature | GUN:GUNB:100:CAVITYWALLRETTEMP*** |
T7 | Nose Temperature | GUN:GUNB:100:NOSETEMP |
T24 | A4 coupler RF Window Temperature | GUN:GUNB:100:A4CPLRRFWNDWTEMP |
T25 | A3 coupler RF Window Temperature | GUN:GUNB:100:A3CPLRRFWNDWTEMP |
T8 | Cathode end cap center temperature | GUN:GUNB:100:CATHENDCAPCENTEMP |
T9 | Cathode end cap outer temperature | GUN:GUNB:100:CATHENDCAPOUTTEMP |
T10 | Anode center temperature | GUN:GUNB:100:ANCENTEMP |
T11 | Anode outer temperature | GUN:GUNB:100:ANOUTTEMP |
T12 | vacuum wall south temperature | GUN:GUNB:100:VACWALLSTEMP |
T13 | vacuum wall north temperature | GUN:GUNB:100:VACWALLNTEMP |
T14 | anode flange ss temperature | GUN:GUNB:100:ANFLANGETEMP |
T15 | cathode end cap outer temperature 2 | GUN:GUNB:100:CATHENDCAPOUTTEMP2 |
T16 | waveguide A3 coupler end temperature | GUN:GUNB:100:WGA3CPLRENDTEMP |
T17 | waveguide A3 middle temperature | GUN:GUNB:100:WGA3MIDTEMP |
T18 | waveguide A3 elbow temperature | GUN:GUNB:100:WGA3ELBOWTEMP |
T19 | waveguide A3 verticle run temperature | GUN:GUNB:100:WGA3VRUNTEMP |
T20 | waveguide A4 coupler end temperature | GUN:GUNB:100:WGA4CPLRENDTEMP |
T21 | waveguide A4 middle temperature | GUN:GUNB:100:WGA4MIDTEMP |
T22 | waveguide A4 elbow temperature | GUN:GUNB:100:WGA4ELBOWTEMP |
T23 | waveguide A4 verticle run temperature | GUN:GUNB:100:WGA4VRUNTEMP | T26 | UV Table temperature 1 | GUN:LGUN:600:UVTABLETEMP1 |
T26 | UV Table temperature 1 | GUN:LGUN:600:UVTABLETEMP1 |
T27 | UV Table temperature 2 | GUN:LGUN:600:UVTABLETEMP2 |
T28 | UV Table temperature 3 | GUN:LGUN:600:UVTABLETEMP3 |
T29 | UV Table temperature 4 | GUN:LGUN:600:UVTABLETEMP4 |
...