Table 1.1

Value

Device Type

SLC-Aware

Controllable

ACCL

Accelerating Section

N

Y

KLYS

Klystron

N

Y

LLRF

Low Level RF

N

Y

PCAV

Beam Phasing Cavity

N

Y

TCAV

Transverse Deflecting Cavity

N

Y

REFS

Machine Parameters Set Points

N

 

Y

 

The following table lists vacuum Compound DeviceTypes:

Table 1.2

Value

Device Type

SLC-Aware

Controllable

VGBA

Vacuum Gauge Baratron

N

N

VGCM

Vacuum Capacitance Manometer

N

Y

VGKL

Vacuum Gauge associated with a Klystron

N

N

VGPR

Vacuum Pirani Gauge

N

N

VGCC

Vacuum Cold Cathode Gauge

N

Y

VGTC

Vacuum ThermoCouple Gauge

N

N

VGCP

Vacuum Convection-enhanced Pirani Gauge

N

N

VGHF

Vacuum Hot Filament Gauge

N

Y

VGOS

Vacuum Overpressure Switch

N

N

VGXX

Combination Vacuum Gauge

N

N

VVKL

Vacuum Valve associated with a Klystron

N

Y

VVPG

Vacuum Pneumatic Gate Valve

N

Y

VVMG

Vacuum Manual Gate Valve

N

N

VVPR

Vacuum Pneumatic Roughing Valve

N

Y

VVMR

Vacuum Manual Roughing Valve

N

N

VVPF

Vacuum Pneumatic Fore Valve

N

Y

VVMF

Vacuum Manual Fore Valve

N

N

VVPV

Vacuum Pneumatic Vent Valve

N

Y

VVMV

Vacuum Manual Vent Valve

N

N

VVFS

Vacuum Fast (Shutter) Valve

N

Y

VVFL

Vacuum (Mass) Flow Valve

N

Y

VPKL

Vacuum Pump associated with a Klystron

N

Y

VPDF

Diffusion Pump

N

N

VPCR

CRyo Pump

N

Y

VPIO

IOn Pump

N

Y

VPTM

TurboMolecular Pump

N

Y

VPTS

Ti Sublimation Pump

N

Y

VPFO

Fore Pump

N

Y

VPRO

Roughing Pump

N

Y

VRGA

Residual Gas Analyzer

N

 

Y

 

The following table lists system Compound DeviceTypes:

...

Table 1.5

Value

Device Type

SLC-Aware

Controllable

APC

All Purpose Controller (e.g. Beckhoff raw signals)

N

Y

BMLN

Beam Line

N

N

CAMW

Web Cam

N

N

CATH

Cathode

N

N

COLL

Collimator

N

Y

DIAG

Diagnostic

N

Y

DUMP

Beam Dump

N

N

EXPT

Experiment

N

Y

FAN

Fan

N

Y

FOIL

Diagnostic Foils, Slotted Foil

N

N

GATT

Gas Attenuator

N

Y

GDET

Gas Detector

N

Y

GUN

Gun

N

Y

HLS

Hydrostatic Leveling Sensor

N

N

KMON

K-monochromator

N

Y

LHTR

Laser Heater

N

N

LION

Long ION chamber

N

N

LVDT

Linear Variable Differential Transformer

N

N

MASK

Mask

N

N

MIRR

Optical Mirror

N

Y

PICS

Protection Ion Chamber Signal

N

N

PICM

MPS Protection Ion Chamber Signal

N

N

PLIC

Panofsky Long Ion Chamber

N

N

PKLS

Pockels Cell (photon attenuation)

N

Y

RADF

RADFET (radiation dose sensor)

N

Y

ROOM

Room, vault, or tunnel

N

N

RTD

Resistive temperature detector

N

N

SATT

Solid Attenuator

N

Y

SBST

Sub-Booster

N

Y

SHUT

Shutter (mechanical, optical shutter)

N

Y

SLIT

Slit (mechanical, 2- or 4-jaw)

N

Y

STPR

Beam Stopper

N

Y

SPLR

Beam Spoiler

N

Y

TRGT

Target

N

Y

TANK

Diagnostic Tank

N

Y

THZR

THz Radiator

N

Y

UTIC

Universal Time Interval Counter

N

Y

TIU

Tone Interrupt Unit (for MPS)

N

N

WIRE

Wire Scanner

N

Y

WKFL

Wakefield Shield

N

Y

XTAL

Crystal Monochromator

N

Y

BKHF

Beckhoff coupler

N

Y

SCTR

Beam Scatterer

N

Y

...

Table 1.10

Area

Physical Location

AS01

Accelerator Structure Test System(ASTA)

LI00

LINAC Sector 0

LR20

LCLS Laser Room (Upstairs, near sector 20)

LA20

FACET Laser Room (Upstairs, near Sector 20)

IN20

Injector

LI20

LINAC Sector 20

LI21

LINAC Sector 21

LI22

LINAC Sector 22

LI23

LINAC Sector 23

LI24

LINAC Sector 24

LI25

LINAC Sector 25

LI26

LINAC Sector 26

LI27

LINAC Sector 27

LI28

LINAC Sector 28

LI29

LINAC Sector 29

LI30

LINAC Sector 30

MCC0

Main Control Center (Bulding 005) OBSOLETE

BSY0

Beam Switchyard Common-line

BSYN

Beam Switchyard North Arc

BSYS

Beam Switchyard South Arc

BSYA

Beam Switchyard A-line

ESA0

End Station A and Beam Dump East

BSYB

Beam Switchyard B-line

LTU0

LINAC-to Undulator Switchyard

LTU1

LINAC-to-Undulator Line 1

UND1

Undulator on Line 1

DMP1

Beam Dump on Line 1

FEE1

Front End Enclosure on Line 1

NEH1

Near Experimental Hall on Line 1

XRT1

X-Ray Tunnel on Line 1

FEH1

Far Experimental Hall on Line 1

XT01

X-Band Test Area

SYS0

LCLS-I System

SYS1

FACET System

SYS2

LCLS-II System

SYS3

LCLS-III System

SYS4

NLCTA System

SYS5

SPEAR Systems

SYS6

X-Band Test Area

SYS7

ASTA Test Area

SYSW

Global System West

SYSE

Global System East

GLB0

Global to all Machines

...

Table 1.11

Area

Position Prefix Codes

Physical Position

LR20

L

Laser Room (Upstairs, near sector 20)

 

IN20

B

Beam Line

 

K

Klystron Gallery

 

W

Waveguide

 

R

RF Equipment Hut

 

L

Laser Line

 

LI20

B

Beam Line

 

W

Waveguide

 

K

Klystron Gallery

 

E

Instrumentation Equipment Alcove

 

LI21

B

Beam Line

 

W

Waveguide

 

K

Klystron Gallery

 

E

Instrumentation Equipment Alcove

 

LI22

B

Beam Line

 

W

Waveguide

 

K

Klystron Gallery

 

E

Instrumentation Equipment Alcove

 

LI23

B

Beam Line

 

W

Waveguide

 

K

Klystron Gallery

 

E

Instrumentation Equipment Alcove

 

LI24

B

Beam Line

 

W

Waveguide

 

K

Klystron Gallery

 

E

Instrumentation Equipment Alcove

 

LI25

B

Beam Line

 

W

Waveguide

 

K

Klystron Gallery

 

E

Instrumentation Equipment Alcove

 

LI26

B

Beam Line

 

W

Waveguide

 

K

Klystron Gallery

 

E

Instrumentation Equipment Alcove

 

LI27

B

Beam Line

 

W

Waveguide

 

K

Klystron Gallery

 

E

Instrumentation Equipment Alcove

 

LI28

B

Beam Line

 

W

Waveguide

 

K

Klystron Gallery

 

E

Instrumentation Equipment Alcove

 

LI29

B

Beam Line

 

W

Waveguide

 

K

Klystron Gallery

 

E

Instrumentation Equipment Alcove

 

LI30

B

Beam Line

 

W

Waveguide

 

K

Klystron Gallery

 

E

Instrumentation Equipment Alcove

 

BSY0

B

Beam Line

 

E

Surface Equipment Building (Bldg 136, 106, 106, 5)

 

P

BSY Pump Station (P0, P1, P2, P3, P5)

 

 

BSYA

B

Beam Line

 

E

Surface Equipment Building (Bldg 136, 106, 106, 5)

 

P

BSY Pump Station (P0, P1, P2, P3, P5)

 

 

BSYB

B

Beam Line

 

E

Surface Equipment Building (Bldg 136, 106, 106, 5)

 

P

BSY Pump Station (P0, P1, P2, P3, P5)

 

 

BSYN

B

Beam Line

 

E

Surface Equipment Building (Bldg 136, 106, 106, 5)

 

P

BSY Pump Station (P0, P1, P2, P3, P5)

 

BSYS

B

Beam Line

 

E

Surface Equipment Building (Bldg 136, 106, 106, 5)

 

P

BSY Pump Station (P0, P1, P2, P3, P5)

 

LTU0

B

Beam Line

 

E

Surface Equipment Building (Bldg 5 or 911)

 

LTU1

B

Beam Line

 

E

Surface Equipment Building (Bldg 105 or Bldg 406 or

 

 

Bldg 911 or Bldg 912 or Bldg 913)

 

MCC0

E

Equipment Rack Area (Bldg 5) OBSOLETE

 

C

Control Room

 

UND1

B

Beam Line

 

E

Surface Equipment Building (Bldg 913,921)

 

DMP1

B

Beam Line

 

E

Surface Equipment Building (Bldg B921)

 

FEE1

B

Beam Line

 

 

Hard (High-energy) through Branch (South) to Hutch 3 and beyond

 

1

Soft (Low-energy) Branch (North) to Hutch 1

 

2

Soft (Low-energy) Branch (Middle) to Hutch 2

 

E

Equipment Rack Alcove or Surface Equipment Building (Bldg 940)

 

NEH1

B

Beam Line

 

 

Hard (High-energy) Branch (South) to Hutch 3 and beyond

 

1

Soft (Low-energy) Branch (North) to Hutch 1

 

2

Soft (Low-energy) Branch (Middle) to Hutch 2

 

E

Surface Equipment Building (Bldg 950)

 

XRT1

B

Beam Line

 

 

Through Branch

 

4

North Branch to Hutch 4

 

5

Middle Branch to Hutch 5

 

6

South Branch to Hutch 6

 

E

Surface Equipment Building (Bldg 960)

 

FEH1

B

Beam Line

 

4

North Branch to Hutch 4

 

5

Middle Branch to Hutch 5

 

6

South Branch to Hutch 6

 

E

Surface Equipment Building (Bldg 999)

XT01

B

Beam Line

 

 

Surface Equipment Building (Bldb 062)

SYS0

 

LCLS-I System

SYS1

 

FACET System

SYS2

 

LCLS-II System

SYS3

 

LCLS-III System

SYS4

 

NLCTA System

SYS5

 

SPEAR System

SYS6

 

X-Band Test Area

SYS7

 

ASTA Test Area

SYSW

 

Global System West

SYSE

 

Global System East

GLB0

 

Global to all Machines

...

Table 1.12

Database Name Subsystem Prefix

Display and Database File Name Subsystem Prefix

Subsystem

CD

generic

Controls Department, for development only!!

LS

lasr

Laser Steering

PM

prof

Profile Monitor

IM

curr

Current Monitor

BL

blen

Bunch Length Monitor

BP

bpm

Beam Position Monitor

MC

mc

Motion Control

CL

coll

Collimator

CV

CAMAC-to-VME

AM

am

Alignment Mirror

MG

mgnt

Magnet

EV

evg or evr

Event (Timing) System

FC

rf/energy

Frequency Counter/Flip Coil

RF

rf

Low-Level RF Master

RP

rf

Low-Level RF PLL

RC

rf

Low-Level RF PAC

RD

rf

Low-Level RF PAD

MP

mps

Machine Protection System

NW

ntwk

Network Device, terminal servers, switches routers

PP

pps

Personnel Protection System

BC

bcs

Beam Containment System

EQ

eq

Equipment: roaming oscilloscopes, function generators, etc. If equipment is to be used for a specific subsystem, then use the subsystem prefix. 

TM

temp

Temperature Monitor

TR

toro

Toroid

TZ

thz

TeraHertz System

VA

vac

Vacuum

WA

wat

Water and HVAC

WS

ws

Wire Scanner

FB

fbck

Feedback

AD

ads

Alignment Diagnostic System (Wire Position Monitors + Hydrostatic Leveling Sensors)

KY

klys

Klystron (Solenoid PS, Modulator PS, PIOP )

EX

ex

Experimental Support

SC

sc

Scope and Oscilloscope Support .

Table 1.12.1

ioc type

ioc

VME IOCs

 

 

 

 

eioc

Embedded IOCs

 

 

 

 

 

sioc

Soft IOCs

 

 

 

 

 

Area

IN20

LI21-LI30

BSY0

LTU1

UND1

DMP1

System

Two character abbreviation for subsystem previx, see Table 1.12

 

 

 

 

 

##

Two digits, Soft ioc-s start at 00-99. All embedded adn VME IOC's start at 01-99.

 

 

 

 

 

...

Panel
  • VVPG:IN20:155 Vacuum valve, pneumatic gate, near the start of the injection area beamline.
  • XCOR:IN20:811 X-axis corrector magnet, near the end of the Gun Spectrometer beamline.
  • YCOR:IN20:812 Y-axis corrector magnet, close to the X-axis corrector.
  • BPMS:IN20:821 Beam Position Monitor, near the end of the Gun Spectrometer beamline, and downstream of the Corrector magnets in the previous example.
  • BEND:IN20:931 Bending dipole magnet near the end of the injection area, in the Injection Spectrometer beam line.

 

Attachments