PVs That Are Normally Within a Range

Raise an alarm if any of these PVs are out of range.

PVUnitLOLOLOHIHIHIDescNotes
BLEN:$(AREA):$(POS):$(INST):SUM       
BLEN:$(AREA):$(POS):$(INST):IMAXA      
BLEN:$(AREA):$(POS):$(INST):TMITpC    Transmitted intensity 
BLEN:$(AREA):$(POS):$(INST):RATEHz    Trigger rate 
BLEN:$(AREA):$(POS):$(INST):Temp0K    Temperature of sensor 0 
BLEN:$(AREA):$(POS):$(INST):Temp1K    Temperature of sensor 1Gap diode only

 

PVs That Are Normally Zero

Raise an alarm if any of these PVs are not zero.

PVDescSeverityNotes
BLEN:$(AREA):$(POS):TmitStatusStatus from BPMINVALIDA copy of TmitStatus0 or TmitStatus1 selected by SelBpm
BLEN:$(AREA):$(POS):BpmStatusReading invalidINVALIDDerived from b31 of StatusOfBsa2
BLEN:$(AREA):$(POS):TmitInvalidTMIT is invalidINVALID 
BLEN:$(AREA):$(POS):TmitSmallTMIT is too smallMAJOR 
BLEN:$(AREA):$(POS):$(INST):SHT_ERRShutter errorMAJORMismatch between control and status. Pyro detector only.
BLEN:$(AREA):$(POS):FLT1_ERRFilter 1 errorMAJORMismatch between control and status. Pyro detector only.
BLEN:$(AREA):$(POS):FLT2_ERRFilter 2 errorMAJORMismatch between control and status. Pyro detector only.
BLEN:$(AREA):$(POS):FLT3_ERRFilter 3 errorMAJORMismatch between control and status. Pyro detector only.
BLEN:$(AREA):$(POS):FLT4_ERRFilter 4 errorMAJORMismatch between control and status. Pyro detector only.

 

PVs That Are Normally Nonzero

Raise an alarm if any of these PVs are zero.

PVDescSeverityNotes
BLEN:$(AREA):$(POS):RxLinkUpRemote server link upINVALIDRemote server is source of BPM
BLEN:$(AREA):$(POS):SrvRemoteIpRemote server IPINVALIDRemote server is source of BPM
BLEN:$(AREA):$(POS):SrvRemotePortRemote server portINVALIDRemote server is source of BPM

 

 