Reason for change:

We request to deploy  AlarmsCfg-07-01-04 in L1proc. In this new tag we relaxed the limits for  the Lac thresholds  of 2 cal channels, and the limit for the pedestal deviation of ACD tile 49 (PMT B)


Test Procedure:

This version of AlarmsCfg has been tested processing locally the monitoring products from two LPA run (753502966 and 748852859).


Rollback procedure:

The package can be rolled back to the previous version by flipping a soft link. Also note that the package is completely independent from any other package running in the pipeline and will not cause a version change of L1Proc.

CCB JIRA:


SSC-468 - Getting issue details... STATUS

Details:

from AlarmsCfg/doc/release.notes:

AlarmsCfg-07-01-04 10-Nov-2024 maldera
- Updating alarm limits on Lac threshold:
       Lac_Thresholds_FaceNeg_TH1_TowerCalLayerCalColumn_3_5_0:  upper warning limit changed from  2.9 to 3.0 (error limit rised from 3.0 to 3.5)
       Lac_Thresholds_FaceNeg_TH1_TowerCalLayerCalColumn_11_1_11:  upper warning limit changed from  2.8 to 2.9  

- Relaxing warning limits for acd ped deviaton for tile 49, pmt B
       AcdPedPedMeanDeviation_PMTB_TH1:  upper warning limit changed from 8 to 10 (for channel 49)  channels 49 and 81 exluded from the computation of the y_rms

Relevant thread: https://www-glast.stanford.edu/protected/mail/datamon/5305.html