Transition to RF off is accomplished with a single sequenced button: “RF Off

  • Open A&P feedback loop
  • Stop following PRL
  • Start tracking cavity frequency
  • Go to pulsed mode by changing duty cycle to 99.85%
  • Turn RF OFF
  • Set buncher chiller Temp Tuning “Feedback Off”
  • Set buncher chiller temperature setpoint to 40 deg C