Instructions (by Davide Caforio)
- Open the Para module (from the GEDI panel, click on Module->Para);
- Click on the "+" symbol alongside the datapoint type you want to
archive;
- The name of the datapoint, together with a "mini folder" symbol, will
appear;
- Click on the "+" symbol. If the datapoint is composed of only one
element then right click on the datapoint name: a scroll-down menu will
appear. Move the pointer to the item "Insert config" and, in the new
scroll-down menu, select "Archive settings";
- An item "_archive" will appear under the datapoint name. Click on it;
- In the pop-up window select "Store original value", then click on the
text field on the right and select "RDB-99) EVENT" (I assume you have the
Oracle database connection setup and active). Depending on the type of
data, you might want to apply a smoothing to the data archived in order to
save disk space: if you select "Smoothing", a list of options will appear.
Usually you will choose a "value dependent smoothing" and hence set the
Deadband value, either on a percentage basis ("relative value") or an
absolute step (0.5 V, 1 mbar etc.);
- Click on OK to accept the changes.
{"serverDuration": 47, "requestCorrelationId": "f62a2e1b5ead2f5d"}