Procedure for turning on the SAGAs
- Ensure the S21 LCS cooling system has sufficient capacity for the SAGAs.
- The cooling system has sufficient capacity if the current usage is at or below
29 kW11 kW. - Open the archiver and load ‘S21_LCS_SAGAs_July_2021.xml’ file to load the correct PVs for the S21 LCS chiller
- The cooling system has sufficient capacity if the current usage is at or below
- The black line is the ‘chiller load’ in kW. You will have to adjust the range for chiller load to 9 to 17 kW. The black line should be below 11 kW when the SAGAs are off.
- The red line (the input water temp) should be < 77 degrees Fahrenheit. It is usually at 63F or below.
How to check that the SAGAs are happy
If the red line is below 77 degrees F and the black line is below 17 kW, then the SAGAs are happy.