Procedure for turning on the SAGAs

  1. Ensure the S21 LCS cooling system has sufficient capacity for the SAGAs.
    1. The cooling system has sufficient capacity if the current usage is at or below 29 kW 11 kW.
    2. Open the archiver and load ‘S21_LCS_SAGAs_July_2021.xml’ file to load the correct PVs for the S21 LCS chiller
  2. The black line is the ‘chiller load’ in kW. You will have to adjust the range for chiller load to 9 to 17 kW. The black line should be below 11 kW when the SAGAs are off.
  3. The red line (the input water temp) should be < 77 degrees Fahrenheit. It is usually at 63F or below.