Login to ppa-clnrm01 (user "tracker") and open a terminal
$ cd /home/tracker/pelle/epics/svt-epics/svt-mpod-epics/
$./run_ioc
This should run the epics IOC and you should see output to the screen.
$ cd /u1/epics/svt-epics/svt-daq-epics
$./run_ioc
This should run the epics IOC and you should see output to the screen. Depending on the debug level (see below) there might be lots of output here. Change the debug level using "mySubDebug" in "example/iocBoot/iocmyexampleApp/st.cmd ".
Login to ppa-pc91245 (user is your normal slac account) and open a terminal
$ cd /u1/epics/svt-epics/svt-medm
Individual GUIs can be opened with:
$ source ./setup_epics.csh
$ medm gui-name.adl & (if you don't add -x it will open in edit mode and you'll have to hit "execute" in one of the windows popping up.
Notes on the hybrid power:
Slot and channel map
Slot | Channel | snmp name | |
---|---|---|---|
0 | X (0-7) | outputUserConfig.uX | |
Y (1-N) | X (0-7) | outputUserConfig.uY0X |
Sense command:
2: use sense for output with medium length cables.
8: do not use sense lines at all
Example below for channel 0-3 on card in slot 0.
# enable ramp down; use sense for regulation; moderate regulation speed (cable length between 1 and 30 m); ignore external inhibit
snmpset -v2c -m +WIENER-CRATE-MIB -c guru ppa-mpod1 outputUserConfig.u0 i 2
snmpset -v2c -m +WIENER-CRATE-MIB -c guru ppa-mpod1 outputUserConfig.u1 i 2
snmpset -v2c -m +WIENER-CRATE-MIB -c guru ppa-mpod1 outputUserConfig.u2 i 2
snmpset -v2c -m +WIENER-CRATE-MIB -c guru ppa-mpod1 outputUserConfig.u3 i 2
outputUserConfig OBJECT-TYPE
SYNTAX Integer32 (0..15)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Definition of user-changeable items.
A bit field packed into an integer which define the behavior of the output channel.
Usable for WIENER LV devices only.
The position of the bit fields in the integer value are:
Bit 0: Voltage ramping at switch off:
0: Ramp down at switch off.
1: No ramp at switch off (immediate off)
Bit 1, 2: Set different regulation modes, dependent on the
cable inductance:
0: fast: short cables, up to 1 meter.
1: moderate: cables from 1 to 30 meter.
2: slow: cables longer than 30 meter.
3: slow (identical to 2, should not be used)
Bit 3: Internal sense line connection to the output (MPOD only):
0: The sense input at the sense connector is used
for regulation.
1: The output voltage is used for regulation.
Any signals at the sense connector are ignored.
Bit 4: External Inhibit input.
0: The external inhibit input is ignored.
1: The external inhibit input must be connected to
a voltage source to allow switch on.
Community required for write access: guru.
"
::= { outputEntry 37 }