You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 7 Next »

TLCMeaningPV
PKDCavity is tuned off frequency so it doesn't affect the beamACCL:{LINAC}:{CM}{CAV}0:PKD
INVInvalid: one of the PVs necessary is not responding to caget or has INVALID status...
ARUAwaiting run up: Station needs attention from LLRF/SRF groups before it can be used. A status set and cleared by expertsTBD
MNTMaintenance: Station is known to be bad and awaiting attention from expertsTBD
HWIHardware Initialization (a.k.a. rack checkout) needs to be run. Don't trust current valuesACCL:{LINAC}:{CM}{CAV}0:HWINITSUM
CKPCheck phase: if something is done to the system that makes 0 phase no longer knowable and ops need to re-phase. A status set and cleared by expertsTBD
SSPSSA Permit: SSA permit to turn on faultedACCL:{LINAC}:{CM}{CAV}0:SSA_LTCH
SSASSA Faulted: SSA not onACCL:{LINAC}:{CM}{CAV}0:SSA:AlarmSummary.SEVR
FROFrequency Offset: LLRF has shifted the frequency - it's offset from nominal. ACCL:{LINAC}:{CM}{CAV}0:FREQ_OFFSET.SEVR
CSICryo Summary Interlock: He Level and He Pressure are summed into the Cryo Summary Interlock in the Resonance/Interlock Chassis. It's faulted.ACCL:{LINAC}:{CM}00:CRYO_LTCH
RLKResonance/Interlock Link faultedACCL:{LINAC}:{CM}{CAV}0:RESLINK_LTCH
FPGFPGA PLL Lock faultACCL:{LINAC}:{CM}{CAV}0:PLL_LTCH
IOCEPICS IOC Watchdog FaultACCL:{LINAC}:{CM}{CAV}0:IOCWDOG_LTCH
BLVBeamline Vacuum too highACCL:{LINAC}:{CM}00:BMLNVACA_LTCH and BMLNVACB_LTCH
CPVCoupler manifold vacuum too highACCL:{LINAC}:{CM}00:CPLRVACA and CPLRVACB
CP1Coupler Temp 1: Temperature sensor on the top of the coupler indicates high tempACCL:{LINAC}:{CM}{CAV}0:CPLRTEMP1_LTCH
CP2Coupler Temp 2: Temperature sensor on the bottom of the coupler indicates high tempACCL:{LINAC}:{CM}{CAV}0:CPLRTEMP2_LTCH
STTStepper motor temp: Temperature sensor on cavity tuner stepper motor out of toleranceACCL:{LINAC}:{CM}{CAV}0:STEPTEMP_LTCH
QCHLLRF system detected a cavity quenchACCL:{LINAC}:{CM}{CAV}0:QUENCH_LTCH
RESResonance Chassis Summary FaultACCL:{LINAC}:{CM}{CAV}0:RESINTLK_LTCH
RFPRF Permit: Latched cavity interlock summary faultACCL:{LINAC}:{CM}{CAV}0:RFPERMIT
PZTHardware summary status for piezoACCL:{LINAC}:{CM}{CAV}0:PZT:HWSTATSUM
STPHardware summary status for stepper motorACCL:{LINAC}:{CM}{CAV}0:STEP:HWSTATSUM
CVCCavity Characterization needs to be run: Due to changes in the LLRF system, the cavity characterization needs to be runACCL:{LINAC}:{CM}{CAV}0:CAV:CALSTATSUM
CTLCavity Controller problem: Cavity LLRF controller misconfigurationACCL:{LINAC}:{CM}{CAV}0:CTRL_SUM.SEVR
RFRRF (not) ready for beam: RFREADYFORBEAM status is faulted, i.e. not in SELAP mode &/or RF is offACCL:{LINAC}:{CM}{CAV}0:RFREADYFORBEAM
PZFPiezo feedback is not onACCL:{LINAC}:{CM}{CAV}0:PZT:MODECTRL
PZOPiezo feedback is indicating a problemACCL:{LINAC}:{CM}{CAV}0:PZT:FBSTATSUM
AFBAmplitude feedback is out of tol: the feedback maintaining the amplitude is unable to keep the amplitude within tolerance.ACCL:{LINAC}:{CM}{CAV}0:AMPFB_SUM
PFBPhase feedback is out of tol: The feedback maintaining the phase is unable to keep the phase within toleranceACCL:{LINAC}:{CM}{CAV}0:PHAFB_SUMF
FBSFeedback Sum: The feedback is unable to keep either phase or amplitude within toleranceACCL:{LINAC}:{CM}{CAV}0:FB_SUM
AMJamplitude jitterTBD
PHJphase jitterTBD
CCRcryomodule cryo - if any statuses from the cryo instrumentation list for specific cavities turn yellow.TBD
???If any analog instrumentation that feeds an interlock turns yellow (CPLRTEMP, vacuum, LL, pressure), show itTBD