Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

  • Pull up the "Long pulse laser operation" screen, and make sure the "StrkCam" is enabled ("DIS" shows as the button option) and the trigger rate is non-zero.  If it is zero, hit the "5 Hz" button to start generating triggers.  (Remember to reset the mode after the IOC has been correctly started.)

  • Make sure the visar is powered and turned on!!!
  • Restart the IOC.  Run "imgr ioc-mec-streak-0${X} --enable" (with ${X} set to either "1" or "2").  The full visar application should start on the PC.
  • Once the IOC has completely started, pull up the edm screen by running "camViewer -m -c Streak_${X}" (with ${X} set to either "1" or "2").
  • Hit the acquire "Start" button on the edm screen.  The PC should open an updating image display window and the image counter on the edm screen should start to increase.  If this doesn't happen, see the trouble shooting guide below.  (If the window does not open on the PC, check the synchronization options.  If the window opens and the image updates but the counter doesn't change, check the scan mode and acquisition options.)

...