namedescriptionsourceunitsnominal value
Tair temp in SVT boxdry air sensorCbetween SVT and room temps
RHrelative humidity in SVT boxdry air sensor%near or below 0
dewdewpoint in SVT boxdry air sensorC-50 or below
flflow switch stateflow switchboolean0 (flow above setpoint)
fSFEB chiller serial linkserial portboolean1 (OK)
sSSVT chiller serial linkserial portboolean1 (OK)
fTFEB chiller tempFEB chiller serial linkCsetpoint +/- 0.1
fSPFEB chiller setpointFEB chiller serial linkC20 - 30
fFlFEB chiller flowFEB chiller serial linkgpm0.30 - 1.0 (this flow meter is not very reliable)
fFFEB chiller fault codeFEB chiller serial link 0 (no errors)
sCSVT chiller stateSVT chiller serial linkboolean1 (running)
sTSVT chiller tempSVT chiller serial linkCsetpoint +/- 0.2
sSPSVT chiller setpointSVT chiller serial linkC-20 - 20
sPwSVT chiller powerSVT chiller serial link% full power15 - 30
sPSVT chiller pressureSVT chiller serial linkbar1.5 - 2.0
io1BNC input voltage 1BNC jackV0 - 5.0

...