Example SNMP commands for switching on/off channels or the crate are in mpod/on.sh and mpod/off.sh.

MPOD will not turn on unless the interlock is plugged in (DB9 on MPOD controller at the left of the crate), turned on (24 V on BK power supply next to chiller), and not tripped (red LED on flow switch = switch is powered and flow is above trip point).

 

Take a calibration run with expert SVT GUI

...