  1. Check the "IRMIS data validation" e-mail title:SUCCESS or FAILED?  If it's SUCCESSful, and there is a subsequent "IRMIS data sync to MCCO completed", then all is well.
  2. If the data validation FAILED:
    1. What does the message for the DATA_VALIDATION step say?  The errors found will be listed.  (e.g. "PV Count drop > 5000", and/or "LCLS Crawler did not complete", etc.)
    2. Refer to the <acc> PV Crawler errors and warnings e-mails.  These show the changes in PV counts by IOC (useful in locating which IOC's PVs count dropped for example)
    3. If needed, go to the logfiles: see "IRMIS data validation" email for the log directory for each crawler.  Also, see table below for logfiles to refer to.

...

At SLAC,

...

what the PV crawlers update

...

, in a nutshell

  • all IRMIS tables in MCCQA. All IRMIS UIs query data on MCCQA: PV and IOC data.
  • 3 production tables on MCCO, which are used by other system – AIDA, BSA applications

...