PLC Setup
MEC JJ Slit Controller
Original Ticket:
Jira | ||||||
---|---|---|---|---|---|---|
|
Motor Configuration Spreadsheet: https://docs.google.com/spreadsheets/d/1HwnSqFijaSIl7dQV-vmsgkornKwyImJqVIbIJrdHJA4/edit?gid=1402490783#gid=1402490783
IOC connection to ioc-mec-mot1 as a static route.
Troubleshooting of the slits: (if they are not working please check these things before calling Peregrine or Christian)
- If the colors on the typhos screen (the screen that is launched after clicking User Devices→JJ Slits) are green but when you move the motor all of the fields turn red
- You have to home all of the axis - to do this click on the expert screen then in the new window scroll down until you see a button labeled cmd_home and click that
- It will ask you to confirm homing of the axis and click yes
- after all of the axis have been homed you should be able to move it normally
- if the screen is all white
- check to see if the plc is online
- from an mec machine you can run $ ping plc-mec-jj-motion
- if that works then you try to restart the ioc - from ioc manager find MEC JJ Slits and click IOC Control→Soft Reboot IOC
- if the plc is not pinging then you can go to User Devices→AC PDU→R68 and check to see if the mec jj slits outlet is on
- if its not on, then you can turn it on and wait about 10 seconds to see if you can ping it
- if the outlet is on and you cant ping it, try turning the outlet on and off and ping again
- if after power cycling the outlet and you cant get it to ping then call controls PoC
- from an mec machine you can run $ ping plc-mec-jj-motion
- check to see if the plc is online
- If none of the steps above worked - contact controls PoC
Old Setup (dumb motor control)
Refer to:
Jira | ||||||
---|---|---|---|---|---|---|
|
Plan: use IMS (user dumb) motors
What are the other motor requirements for Smith L-10075?
- Nothing special. Standard configuration (quads, sample hexapod/stage)
Need:
- Slits: in cabinet or TC?
- Vacuum cables (4)
- Verify presence and type of vacuum cables (28 Sept)
- Available flange ports (4)
- Verify (28 Sept)
- Air cables (4)
- Talk to Vincent (e-mailed on 27 Sept)
- Available IMS motor channels (4)
- Identify
- To PR60 patch panel and/or direct to MForce chassis
- Parameter manager settings
- Christian to follow up with Vincent (some JJ Slit related XCS stage in pmgr)