  1. Set the piezo to feedback
  2. Set the RF mode to SELA
  3. If the cavity is off, set the amplitude to 5MV and turn it on
  4. Walk the amplitude in steps of 0.5MV up to 10MV and steps of 0.1MV above 10MV
    1. Raise an error if the quench interlock is latched
  5. Set the RF mode to SELAP

Using the Program

Info
Unless you understand the necessary ordering of steps, always keep all options at the top selected (this is the default). Running the subscripts out of order can have unintended consequences.

This program is designed to simplify the turn on script into a "one button turn-on." You can set up an individual cavity, an entire cryomodule, or an entire linac section at once.

Demos

Info

Note that these demos were all recorded using simulated data on a personal machine; the production version has slight aesthetic differences.


Full Cryomodule Setup

Navigate to the desired cryomodule by selecting the appropriate linac and CM tabs, then press the cryomodule setup button