- Set the pulsed drive level to 15%
- Run a cavity characterization
- Raise an error if the characterization crashed
- Raise an error if the loaded Q is not within 2.5e7 and 5.1e7
- Raise an error if the cavity scale factor is not within 10 and 125
- Push the loaded Q and cavity scale factor
- Reset the data decimation to 255 for both CW and pulsed
- Reset the piezo feedback set point to 0
- Run the cavity probe Q calculation
Cavity Ramp-Up
- Set the piezo to feedback
- Set the RF mode to SELA
- If the cavity is off, set the amplitude to 5MV and turn it on
- Walk the amplitude in steps of 0.5MV up to 10MV and steps of 0.1MV above 10MV
- Raise an error if the quench interlock is latched
- Set the RF mode to SELAP
...