Using a previously saved drive max found during initial cryomodule commissioning as a starting point (or 1 for the harmonic linearizers), it recursively runs an SSA calibration with decreasing drive max until either the calibration succeeds or the it hits one of two fault conditions:

  • The max forward power

...

  • is less than 3kW

...

  • The desired drive max is less than 0.5